Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00327 FIR-Aging Inspection7/30/20107/30/20107/30/2010 3:04:37 PM FAIL
Need access to verify ceiling install per notes dated 5/20/09.
FIR10-00370 INSP-Final Inspection7/29/20107/30/20107/30/2010 3:01:16 PMPPASS
Fire alarm permit final approved. Record of completion reports pending.
FIR10-00358 INSP-Sprinkler Rough-in7/30/20107/30/20107/30/2010 3:00:11 PMPFAIL
See stamped plans on site for annotations and locations of correction items including one pendent head missing at classroom 129, blocked uprights at class 109, 1/2" extenders at drops in the community room 105, one leaking drop/armover at classroom 110.
FIR10-00163 INSP-Final Inspection7/30/20107/30/20107/30/2010 2:55:46 PMPNR
tim Phone #: ###-#### Per contractor inspection request was intended for FIR10-00161.
FIR10-00161 INSP-Final Inspection7/30/20107/30/20107/30/2010 2:54:09 PMPPASS
Corrections completed, fire alarm inspection passed. Permit finaled.
BLD10-00357 FIRE-Final Inspection7/29/20107/30/20107/30/2010 2:52:43 PMPPASS
Life safety passed, one exit sign repaired while on site.
BLD09-01820 FIRE-Final Inspection7/29/20107/30/20107/30/2010 2:51:31 PMAPASS
Fire life safety finaled.