BLD10-00990
| FIRE-Conference | 7/30/2010 | 7/30/2010 | 7/30/2010 3:33:13 PM | P | DONE |
|
|
Consulted on proximity of partition pilaster to sprinkler head.
|
MIS10-00226
| FIR-Conference | 7/30/2010 | 7/30/2010 | 7/30/2010 2:42:20 PM | A | DONE |
|
|
While performing a fire alarm inspection I noticed that what appeared to be a freshly cut up interior wall was piled/leaning against an exterior roll up door. I went into the business and spoke to the owner about the need for permits for the work being done. He showed me where mezzanine floor area was being increased over the interior exit stairs. I let him know that this work has the potential to effect sprinkler and/or fire alarm devices.
|
BLD10-01260
| BLD-Final | 7/30/2010 | 7/30/2010 | 7/30/2010 2:35:36 PM | P | PASS |
|
|
Life safety passed. Fire alarm is complete
|
FIR10-00364
| INSP-Final Inspection | 7/30/2010 | 7/30/2010 | 7/30/2010 2:34:55 PM | P | PASS |
|
|
Permit finaled
|
FIR10-00364
| INSP-Alarm Testing | 7/29/2010 | 7/30/2010 | 7/30/2010 2:33:22 PM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Robert Gobler
|
FIR10-00307
| INSP-Final Inspection | 7/30/2010 | 7/30/2010 | 7/30/2010 1:29:21 PM | P | FAIL |
|
|
Bill was not available to do the inspection. No one was on site either. No inspection was performed.
|
FIR10-00322
| INSP-Sprinkler Rough-in | 7/29/2010 | 7/30/2010 | 7/30/2010 11:36:11 AM | A | PASS |
|
|
The front lobby hardlid area piping is ok to cover. The earthquaking needs addressed. The earthquake detail were not legible. Clearer details need to be provided at the next inspection.
|
FIR10-00199
| INSP-Sprinkler Rough-in/Hydro | 7/29/2010 | 7/30/2010 | 7/30/2010 11:34:34 AM | A | PASS |
|
|
Permit finaled
|
BLD10-01621
| BLD-Final | 7/30/2010 | 7/30/2010 | 7/30/2010 10:05:49 AM | A | PASS |
|
|
Life safety passed.
|
FIR10-00166
| INSP-Final Inspection | 7/29/2010 | 7/30/2010 | 7/30/2010 10:00:41 AM | A | FAIL |
|
|
The panel is transmitting fire alarm and supervisory signals but has not been set up to provide a trouble signal as required. The netcon was a 5.
|
FIR10-00167
| INSP-Final Inspection | 7/29/2010 | 7/30/2010 | 7/30/2010 9:53:49 AM | A | PASS |
|
|
Permit finaled. The netcon was a 5.
|
FIR10-00172
| INSP-Final Inspection | 7/29/2010 | 7/30/2010 | 7/30/2010 9:53:08 AM | A | FAIL |
|
|
The address on the building does not match the permit address. This will have to be corrected. All other items are passed. The netcon was a 5.
|
FIR10-00173
| INSP-Final Inspection | 7/29/2010 | 7/30/2010 | 7/30/2010 9:52:42 AM | A | FAIL |
|
|
The address on the building does not match the permit address. This will have to be corrected. All other items are passed. The netcon was a 5.
|
FIR10-00171
| INSP-Final Inspection | 7/29/2010 | 7/30/2010 | 7/30/2010 9:50:47 AM | A | PASS |
|
|
Permit finaled. The netcon was a 5.
|
FIR10-00225
| INSP-Alarm Testing | 7/29/2010 | 7/30/2010 | 7/30/2010 9:49:59 AM | A | DONE |
|
|
Phase 13 fire alarm passed. The wall mount a/v needed to be increased to 95cd to meet spacing requirements.
|
BLD09-00945
| FIRE-Final Inspection | 7/29/2010 | 7/30/2010 | 7/30/2010 9:48:50 AM | A | FAIL |
|
|
Todays inspection was for phase 13. Life safety passed in this area.
|
FIR10-00238
| INSP-Sprinkler Rough-in/Hydro | 7/29/2010 | 7/30/2010 | 7/30/2010 12:00:00 AM | A | CANC |
|
|
justin Phone #: ###-####//cancelled per Justin 7/30 @ 7:18am
|
FIR10-00262
| INSP-Sprinkler Rough-in/Hydro | 7/29/2010 | 7/30/2010 | 7/30/2010 12:00:00 AM | A | CANC |
|
|
justin Phone #: ###-####//cancelled per Justin 7/30 @ 7:18am
|