Inspections for the day of: Friday, July 30, 2010.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD10-00990 FIRE-Conference7/30/20107/30/20107/30/2010 3:33:13 PMPDONE
Consulted on proximity of partition pilaster to sprinkler head.
MIS10-00226 FIR-Conference7/30/20107/30/20107/30/2010 2:42:20 PMADONE
While performing a fire alarm inspection I noticed that what appeared to be a freshly cut up interior wall was piled/leaning against an exterior roll up door. I went into the business and spoke to the owner about the need for permits for the work being done. He showed me where mezzanine floor area was being increased over the interior exit stairs. I let him know that this work has the potential to effect sprinkler and/or fire alarm devices.
BLD10-01260 BLD-Final7/30/20107/30/20107/30/2010 2:35:36 PMPPASS
Life safety passed. Fire alarm is complete
FIR10-00364 INSP-Final Inspection7/30/20107/30/20107/30/2010 2:34:55 PMPPASS
Permit finaled
FIR10-00364 INSP-Alarm Testing7/29/20107/30/20107/30/2010 2:33:22 PMAPASS
Phone #: ###-#### >> Inspection requested via web by Robert Gobler
FIR10-00307 INSP-Final Inspection7/30/20107/30/20107/30/2010 1:29:21 PMPFAIL
Bill was not available to do the inspection. No one was on site either. No inspection was performed.
FIR10-00322 INSP-Sprinkler Rough-in7/29/20107/30/20107/30/2010 11:36:11 AMAPASS
The front lobby hardlid area piping is ok to cover. The earthquaking needs addressed. The earthquake detail were not legible. Clearer details need to be provided at the next inspection.
FIR10-00199 INSP-Sprinkler Rough-in/Hydro7/29/20107/30/20107/30/2010 11:34:34 AMAPASS
Permit finaled
BLD10-01621 BLD-Final7/30/20107/30/20107/30/2010 10:05:49 AMAPASS
Life safety passed.
FIR10-00166 INSP-Final Inspection7/29/20107/30/20107/30/2010 10:00:41 AMAFAIL
The panel is transmitting fire alarm and supervisory signals but has not been set up to provide a trouble signal as required. The netcon was a 5.
FIR10-00167 INSP-Final Inspection7/29/20107/30/20107/30/2010 9:53:49 AMAPASS
Permit finaled. The netcon was a 5.
FIR10-00172 INSP-Final Inspection7/29/20107/30/20107/30/2010 9:53:08 AMAFAIL
The address on the building does not match the permit address. This will have to be corrected. All other items are passed. The netcon was a 5.
FIR10-00173 INSP-Final Inspection7/29/20107/30/20107/30/2010 9:52:42 AMAFAIL
The address on the building does not match the permit address. This will have to be corrected. All other items are passed. The netcon was a 5.
FIR10-00171 INSP-Final Inspection7/29/20107/30/20107/30/2010 9:50:47 AMAPASS
Permit finaled. The netcon was a 5.
FIR10-00225 INSP-Alarm Testing7/29/20107/30/20107/30/2010 9:49:59 AMADONE
Phase 13 fire alarm passed. The wall mount a/v needed to be increased to 95cd to meet spacing requirements.
BLD09-00945 FIRE-Final Inspection7/29/20107/30/20107/30/2010 9:48:50 AMAFAIL
Todays inspection was for phase 13. Life safety passed in this area.
FIR10-00238 INSP-Sprinkler Rough-in/Hydro7/29/20107/30/20107/30/2010 12:00:00 AMACANC
justin Phone #: ###-####//cancelled per Justin 7/30 @ 7:18am
FIR10-00262 INSP-Sprinkler Rough-in/Hydro7/29/20107/30/20107/30/2010 12:00:00 AMACANC
justin Phone #: ###-####//cancelled per Justin 7/30 @ 7:18am