Inspections for the day of: Wednesday, July 30, 2014.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-02747 ELE-Aging Inspection7/30/20147/30/20147/31/2014 11:39:53 AM CANC
ELE12-00777 ELE-Aging Inspection7/30/20147/30/20147/31/2014 11:16:51 AM DONE
Service chnge covered on permit ele12-01145
ELE14-01574 Final7/30/20147/30/20147/30/2014 2:48:50 PMPPASS
Justin Phone #: ###-#### UL listing confirmed Final ok
ELE14-01881 Electrical Rough-In7/29/20147/30/20147/30/2014 1:40:28 PMPPASS
Please inspect underground conduit for cover. Thank you Phone #: ###-#### >> Inspection requested via web by Thomas Jenkins Under ground from control room to well, and control room floor rough in ok cover
ELE14-02003 Electrical Rough-In7/29/20147/30/20147/30/2014 1:12:20 PMPPASS
Please inspect 6 pole bases and conduit. Thank you Phone #: ###-#### >> Inspection requested via web by Thomas Jenkins Rough in ok cover
ELE14-01591 Final7/30/20147/30/20147/30/2014 12:43:31 PMPPASS
Phone #: ###-#### >> Inspection requested via web by HZ ZAHIC Final ok
ELE14-01963 Electrical Rough-In7/30/20147/30/20147/30/2014 12:05:01 PMPPASS
Underground rough-in. Phone #: ###-#### >> Inspection requested via web by Rafael Castillo Far N. E. corner as noted on contractor print under ground rough in ok cover
ELE14-01361 Final7/29/20147/30/20147/30/2014 11:18:33 AMAPASS
Mike Dale - ###-#### or Cory ###-#### Phone #: ###-#### >> Inspection requested via web by Cyndi Dale Final ok
GCE14-00113 GCE-Rough-In7/29/20147/30/20147/30/2014 10:46:17 AMAPASS
###-#### Final ok
GCE14-00089 GCE-Final7/29/20147/30/20147/30/2014 10:14:34 AMAPASS
Rick ###-#### Final ok
GCE14-00040 GCE-Rough-In7/29/20147/30/20147/30/2014 9:53:16 AMAFAIL
Steve ###-#### 300.4- MC when ran through bored holes that do not maintain 1 1/4" from framing surface protection from physical damage shall be installed.
300.11- Luminaires and outlet boxes shall have indepenant support form ceiling support system.
300.11- Luminaires and outlet boxes shall be independantly supported from ceiling support system.
ELE14-02045 Electrical Rough-In7/29/20147/30/20147/30/2014 9:02:15 AMAPASS
Swimming pool electrical ( ug & bonding)
(3) bonds
(3) low voltage lights
Access through orange temporary fence on Engelmann Dr side of house Phone #: ###-#### >> Inspection requested via web by Lars Johnson Rough in ok cover
ELE14-01529 Final7/29/20147/30/20147/30/2014 8:41:20 AMAPASS
>> Inspection requested via web by daniel bibikov Final ok