Inspections for the day of: Wednesday, July 30, 2014.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00228 INSP-Sprinkler Rough-in7/30/20147/30/20147/30/2014 3:27:18 PMPPASS
See the city approved plans for new rooms ok to cover.
FIR13-00612 INSP-Supply line flush7/29/20147/30/20147/30/2014 3:10:59 PMAPASS
Supply line flush passed
FIR14-00335 INSP-Final Inspection7/29/20147/30/20147/30/2014 2:26:01 PMAFAIL
Alarm signals activated by the flow switches are automatic resetting and the FACP is in trouble due to a missing phone line.
BLD14-00728 FIRE-Final Inspection7/29/20147/30/20147/30/2014 2:24:31 PMAFAIL
Need the project related fire alarm permit finaled and signage on the riser room door.
FIR14-00314 INSP-Final Inspection7/29/20147/30/20147/30/2014 10:24:39 AMAPASS
Permit finaled
FIR14-00256 INSP-Sprinkler Rough-in7/29/20147/30/20147/30/2014 10:23:21 AMAPART
Rough-in inspection was for the three story existing office area. I noted three areas where upright springklers are blocked.
FIR14-00316 INSP-Sprinkler Rough-in7/28/20147/30/20147/30/2014 10:19:30 AMACANC
Cancel per Roy
BLD13-03346 FIRE-Final Inspection7/28/20147/30/20147/30/2014 10:08:44 AMAPART
A temporary occupancy was given with scott arellano's permission until: Exit sign at front double door is repaired, ADA hardware for both restrooms, dead bolt removed from rear exit door, occupant load sign posted. Also per discussion with Lee and Scott the single ceiling mounted horn/strobe needs to be removed or additional devices provided. This work does require a permit.
FIR14-00216 INSP-Final Inspection7/25/20147/30/20147/30/2014 10:07:36 AMAPASS
Permit finaled