FIR14-00898
| INSP-Final Inspection | 7/29/2015 | 7/30/2015 | 7/30/2015 4:38:13 PM | P | PART |
|
|
Initial fire alarm system testing, including all fire sprinkler interface for wet-pipe systems, SDs SFD, etc. Dry pipe systems not tested yet, including trip test of dry-pipe valves.
|
FIR14-00815
| INSP-Final Inspection | 7/29/2015 | 7/30/2015 | 7/30/2015 4:36:17 PM | P | CANC |
|
|
Ran out of time for this inspection. Will inspect first thing tomorrow morning as fire alarm testing continues.
|
FIR14-00815
| INSP-Alarm Testing | 7/29/2015 | 7/30/2015 | 7/30/2015 4:34:59 PM | A | PART |
|
|
Partial fire alarm system inspection for wet fire sprinklers, including all risers, except for the clubhouse. All waterflows, tampers, etc, tested OK
|
FIR14-00603
| INSP-Alarm Testing | 7/29/2015 | 7/30/2015 | 7/30/2015 4:33:19 PM | A | PART |
|
|
Partial fire alarm interface testing, including all wet pipe systems, except for the clubhouse, including water flows, tampers, etc.
|
FIR14-00070
| INSP-Sprinkler Rough-in/Hydro | 7/29/2015 | 7/30/2015 | 7/30/2015 1:06:56 PM | A | CANC |
|
|
Wrong permit # called in for this inspection. See permit # FIR14-00750 for inspection conducted today (7/30).
|
FIR14-00750
| INSP-Sprinkler Rough-in/Hydro | 7/30/2015 | 7/30/2015 | 7/30/2015 1:04:55 PM | P | PASS |
|
|
Hydrotest and RTC inspection for Bldg. K wet-pipe system (200psi @ 2hrs). PASSED = OK to cover pipe for this system.
|
FIR14-00070
| INSP-Sprinkler Rough-in | 7/29/2015 | 7/30/2015 | 7/30/2015 1:02:03 PM | A | CANC |
|
|
Wrong permit called in for this inspection - see permit # FIR14-00750 for inspections conducted today (7/30).
|
FIR15-00096
| INSP-Sprinkler Rough-in | 7/29/2015 | 7/30/2015 | 7/30/2015 12:59:00 PM | A | PART |
|
|
RTC 2nd floor corridors - all sections. PASSED - OK to cover sprinkler pipe in this area.
|