Inspections for the day of: Thursday, July 30, 2015.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorThomas Walsh
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00898 INSP-Final Inspection7/29/20157/30/20157/30/2015 4:38:13 PMPPART
Initial fire alarm system testing, including all fire sprinkler interface for wet-pipe systems, SDs SFD, etc. Dry pipe systems not tested yet, including trip test of dry-pipe valves.
FIR14-00815 INSP-Final Inspection7/29/20157/30/20157/30/2015 4:36:17 PMPCANC
Ran out of time for this inspection. Will inspect first thing tomorrow morning as fire alarm testing continues.
FIR14-00815 INSP-Alarm Testing7/29/20157/30/20157/30/2015 4:34:59 PMAPART
Partial fire alarm system inspection for wet fire sprinklers, including all risers, except for the clubhouse. All waterflows, tampers, etc, tested OK
FIR14-00603 INSP-Alarm Testing7/29/20157/30/20157/30/2015 4:33:19 PMAPART
Partial fire alarm interface testing, including all wet pipe systems, except for the clubhouse, including water flows, tampers, etc.
FIR14-00070 INSP-Sprinkler Rough-in/Hydro7/29/20157/30/20157/30/2015 1:06:56 PMACANC
Wrong permit # called in for this inspection. See permit # FIR14-00750 for inspection conducted today (7/30).
FIR14-00750 INSP-Sprinkler Rough-in/Hydro7/30/20157/30/20157/30/2015 1:04:55 PMPPASS
Hydrotest and RTC inspection for Bldg. K wet-pipe system (200psi @ 2hrs).
PASSED = OK to cover pipe for this system.
FIR14-00070 INSP-Sprinkler Rough-in7/29/20157/30/20157/30/2015 1:02:03 PMACANC
Wrong permit called in for this inspection - see permit # FIR14-00750 for inspections conducted today (7/30).
FIR15-00096 INSP-Sprinkler Rough-in7/29/20157/30/20157/30/2015 12:59:00 PMAPART
RTC 2nd floor corridors - all sections.
PASSED - OK to cover sprinkler pipe in this area.