FIR15-00182
| INSP-Supply line flush | 7/30/2015 | 7/30/2015 | 7/30/2015 2:23:34 PM | P | PART |
|
|
This inspection was not a supply line flush, this was an underground fire line cover inspection, piping installed approved for cover, talked to point of contact, Jeremy, phone ###-####, still has more piping to install for the underground supply, will schedule another inspection when installed.
|
FIR15-00486
| INSP-Sprinkler Rough-in/Hydro | 7/30/2015 | 7/30/2015 | 7/30/2015 12:55:20 PM | P | CANC |
|
|
Cancelled by contractor when contacted, valve leaking by on city side, contractor will reshedule inspection after repair is made.
|
NAF15-00017
| INSP-Sprinkler Rough-in/Hydro | 7/29/2015 | 7/30/2015 | 7/30/2015 10:53:12 AM | A | PASS |
|
|
Underground hydrostatic test passed/complete
|
BLD15-01844
| FIRE-Final Inspection | 7/24/2015 | 7/30/2015 | 7/30/2015 9:59:33 AM | A | CANC |
|
|
Tenant not ready for final inspection, contractor will reschedule inspection when finished/ready
|
BLD15-00868
| FIRE-Final Inspection | 7/29/2015 | 7/30/2015 | 7/30/2015 9:32:57 AM | A | PASS |
|
|
Life fire safety passed/complete
|