MIS18-00286
| ELE-Conference | 7/30/2018 | 7/30/2018 | 7/30/2018 2:37:49 PM | P | DONE |
|
|
Elc work being done without a permit per Bill Phone #: ###-#### Unable to confirm complaint. Tried front door, no answer, left correction notice asking owner to call. Will check back 8-1
|
ELE18-02739
| Permanent Service | 7/27/2018 | 7/30/2018 | 7/30/2018 2:18:46 PM | P | PASS |
|
|
Please call Brandon 45 min before inspection thanks Phone #: ###-#### Inspection requested via web by Kelly Tarter 46k previously stated was value at transformer. 5779 value posted. p/s u/g rec ok
|
ELE18-02736
| Permanent Service | 7/27/2018 | 7/30/2018 | 7/30/2018 2:04:45 PM | P | PASS |
|
|
Please call Brandon 45 min before inspection.
Thanks Phone #: ###-#### Inspection requested via web by Kelly Tarter 46k previously stated is value at transformer. 15,900 value posted. p/s u/g rec ok
|
ELE18-02737
| Permanent Service | 7/30/2018 | 7/30/2018 | 7/30/2018 1:59:02 PM | P | PASS |
|
|
Available fault current update, 46K previously stated was at transformer. 65k rated gear being installed. p/s u/g rec ok
|
ELE18-01789
| Final | 7/30/2018 | 7/30/2018 | 7/30/2018 1:37:49 PM | P | PASS |
|
|
Troy Phone #: ###-#### Final ok
|
ELE17-02862
| Electrical Rough-In | 7/30/2018 | 7/30/2018 | 7/30/2018 1:37:09 PM | A | PASS |
|
|
5TH floor hallway drop ceilings Phone #: ###-#### Inspection requested via web by Tom Betty Misc storage rooms to have surface mount luminaires. OK Corridor drop lids rough in ok cover.
|
ELE18-02826
| Electrical Rough-In | 7/25/2018 | 7/30/2018 | 7/30/2018 12:05:07 PM | A | NH |
|
|
Please call 1hr ahead for access, meet near elevator on 1st floor - Donny Phone #: ###-#### Called contact at 10:30 and left message I would be at location at 11:30 or shortly after. Arrived at location at 11:50 and called contact, no answer, left message to recall when accessible. no return calls.
|
ELE18-01931
| Final | 7/29/2018 | 7/30/2018 | 7/30/2018 9:07:24 AM | A | PASS |
|
|
Call for access Phone #: ###-#### Inspection requested via web by John VanZandt Final ok
|
ELE18-01885
| Final | 7/29/2018 | 7/30/2018 | 7/30/2018 9:06:03 AM | A | PASS |
|
|