Inspections for the day of: Tuesday, July 30, 2019.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTom Saunders
TitleELE-INSPECTOR
Phone #208-794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-03646 Final7/30/20197/30/20197/30/2019 2:48:27 PMPFAIL
Leon Phone #: ###-####...
too many corrections
pool power needs addressed
no GFCI protection
ELE19-01402 Final7/30/20197/30/20197/30/2019 1:15:53 PMPCANC
Phone #: ###-#### Inspection requested via web by Don Conley...ok to final
ELE19-00465 Final7/30/20197/30/20197/30/2019 12:19:16 PMPPASS
Phone #: ###-#### Inspection requested via web by David Nelson...
corrections made...ok to final
ELE19-02746 Final7/30/20197/30/20197/30/2019 11:52:10 AMPPASS
listing inspection for solar equipment.

this inspection is for an addition that was done a couple years ago, to an existing array, that somehow fell through the cracks. Phone #: ###-#### Inspection requested via web by Ryan King...wiring was sized on original install on permit ELE15-02150...added panels complete..ok to final
ELE19-02746 Electrical Rough-In7/25/20197/30/20197/30/2019 11:49:57 AMPPASS
listing inspection for solar equipment.

this inspection is for an addition that was done a couple years ago, to an existing array, that somehow fell through the cracks. Phone #: ###-#### Inspection requested via web by Ryan King...
UL listed equipment added to existing rays..ok
ELE19-01763 Final7/29/20197/30/20197/30/2019 11:25:46 AMPPASS
Phone #: ###-#### Inspection requested via web by TOM BICANDI...ok to final
ELE19-02280 Final7/29/20197/30/20197/30/2019 11:01:15 AMAPART
Final Inspection for occupancy of the Middle School ONLY -

Contact Chris Kriewall for access to Middle School Phone #: ###-#### Inspection requested via web by JENNY EMEL...
temp occupency for this half...lighting retro with UL listed lights...projector outlets moved using existing circuit
ELE19-02810 Final7/29/20197/30/20197/30/2019 10:04:43 AMAPASS
Add 240v 20 amp circuit for steam humidifier Phone #: ###-#### Inspection requested via web by Jason Gaythwaite....
circuit added thru attic and on surface to unit
complete...ok to final
ELE19-02807 Electrical Rough-In7/29/20197/30/20197/30/2019 9:43:22 AMAPASS
Phone #: ###-#### Inspection requested via web by Jeremy Cloud...
ok to cover...new furred out wall, underground pipe fix, and kitchen area ceiling
excluding ceiling at back entry and halls...need future inspections
ELE19-01891 Electrical Rough-In7/30/20197/30/20197/30/2019 9:18:43 AMAPASS
grid cover...ok for TI and shell under permit ELE19-01892
ELE19-01892 Electrical Rough-In7/29/20197/30/20197/30/2019 9:16:59 AMAPASS
Please call 30 mins prior Phone #: ###-#### Inspection requested via web by Kerri Hamilton...grid ok to cover...sysmic wires added in space...no major reconfiguration...TI permit ok as well ELE19-01891
ELE19-02800 Final7/29/20197/30/20197/30/2019 8:35:30 AMAPASS
i will plan to be there between 8:30-9:30. if earlier will work out please let me know, or later, i can arrange to meet at site. only reason is its behind the fence and also the dog is out there sometimes. thank you Phone #: ###-#### Inspection requested via web by Taras Shulga..
new circuit ran on exterior of building...15A....nonfused disconnect
ok to final