ELE01-02550
| Electrical Rough-In | 7/30/2001 | 7/31/2001 | 7/31/2001 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 07/30/2001 at 12:09:16. Contact: . walls and hard ceiling no grid ceiling 7/30/2001 4:54:17 PM
|
ELE01-02453
| Electrical Rough-In | 7/30/2001 | 7/31/2001 | 7/31/2001 12:00:00 AM | A | CANC |
|
|
Scheduled by a contractor via Hello! on 07/30/2001 at 12:11:00. Contact: ###-####. canc 7/31/2001 12:54:12 PM needs p/s not r/i see added p/s inspection request 7/31/2001 12:54:51 PM
|
ELE01-02224
| Final | 7/30/2001 | 7/31/2001 | 7/31/2001 12:00:00 AM | A | FAIL |
|
|
###-#### partial final see JF for details 110-26 for panel needs grd rods 250-32 225 part B for panel feed and light feed called, contractor is getting info 7/31/2001 11:27:30 AM
|
ELE01-02543
| Electrical Rough-In | 7/30/2001 | 7/31/2001 | 7/31/2001 12:00:00 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 07/30/2001 at 15:29:03. Contact: ###-####. r/i ok, conference ok 7/31/2001 2:10:03 PM
|
ELE01-02574
| Electrical Rough-In | 7/30/2001 | 7/31/2001 | 7/31/2001 12:00:00 AM | A | PART |
|
|
partial r/i Kay ###-#### #140 WALLS AND HARD CEILING 1ST FLOOR 7/31/2001 10:33:21 AM
|
ELE01-02576
| Electrical Rough-In | 7/30/2001 | 7/31/2001 | 7/31/2001 12:00:00 AM | A | NR |
|
|
john ###-#### called need to meet contractor at job site, he will arange a meeting with me do not cover posted 7/31/2001 2:40:30 PM
|
ELE01-01456
| Electrical Rough-In | 7/31/2001 | 7/31/2001 | 7/31/2001 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 07/31/2001 at 07:15:35. Contact: ###-####. CEILING OK 7/31/2001 10:05:04 AM
|
ELE01-02584
| Rough-In Permanent Service | 7/31/2001 | 7/31/2001 | 7/31/2001 12:00:00 AM | P | FAIL |
|
|
###-#### cor. and do not cover posted called 210-70(2), 300-4, 336-16, 210-52(c) (1) outlet spacing right and left of kit. sink both units,110-3(b) and 110-14(b) needs to use listed tool for crimp sleves 8/1/2001 10:02:07 AM
|
ELE01-01768
| Final | 7/31/2001 | 7/31/2001 | 7/31/2001 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 07/31/2001 at 10:37:19. Contact: ###-####. ok 7/31/2001 4:23:52 PM
|
ELE01-01222
| Rough-In Permanent Service | 7/31/2001 | 7/31/2001 | 7/31/2001 12:00:00 AM | P | FAIL |
|
|
###-#### cor. posted 370-16, 300-14, 300-4, 210-11(c)(3), 210-52(a) needs 200 amp meterbase u bolt or guy kit and proper clearence from drip loop to roof 7/31/2001 3:59:32 PM
|
ELE01-02587
| Final | 7/31/2001 | 7/31/2001 | 7/31/2001 12:00:00 AM | P | FAIL |
|
|
6 recepticals and 12 curcuits for postal annex in the fred meyers-Please do early pm structural and fire will be going out today pm 1-###-#### Ken cor.posted at panel called if ? see JF 7/31/2001 5:26:47 PM
|
ELE01-02453
| Permanent Service | 7/31/2001 | 7/31/2001 | 7/31/2001 12:00:00 AM | P | PASS |
|
|
Added by Inspector: 315 On 7/31/2001 12:55:22 PM p/s u/g new ok
|