FIR05-00517
| FIR-Aging Inspection | 7/31/2006 | 7/31/2006 | 8/2/2006 1:39:08 PM | | DEFR |
|
|
|
FIR05-00425
| INSP-Sprinkler Rough-in/Hydro | 7/31/2006 | 7/31/2006 | 8/1/2006 3:46:30 PM | P | PART |
|
|
OH rough-in at the hotel lobby drop ceiling areas as noted are okay to cover, two heads in the hard lid above reception counter do not meet min. spacing req.
|
FIR06-00303
| INSP-Supply line flush | 7/31/2006 | 7/31/2006 | 8/1/2006 7:34:20 AM | P | PART |
|
|
UG fire supply line flush performed satisfactory.
|
FIR06-00476
| INSP-Sprinkler Rough-in | 7/28/2006 | 7/31/2006 | 7/31/2006 2:49:22 PM | P | PART |
|
|
OH rough-in is okay to cover, noted two sprinkler heads in the basement which will require relocation for proper spacing and coverage.
|
FIR06-00394
| INSP-Final Inspection | 7/28/2006 | 7/31/2006 | 7/31/2006 2:44:02 PM | A | PASS |
|
|
Duct detector has been moved to an approved location, fire alarm tested satisfactory.
|
FIR06-00481
| INSP-Final Inspection | 7/30/2006 | 7/31/2006 | 7/31/2006 2:19:00 PM | A | FAIL |
|
|
One pendent head above office next to ductwork is damaged and needs to be replaced, remove plastic shipping guards from heads in 4 locations, provide missing 2nd pc canopy at 401 in restroom.
|
BLD06-00276
| FIRE-Final Inspection | 7/31/2006 | 7/31/2006 | 7/31/2006 12:32:52 PM | P | PASS |
|
|
Items on correction notice have been verified for completion, life safety passed inspection.
|
FIR06-00451
| INSP-Sprinkler Rough-in/Hydro | 7/30/2006 | 7/31/2006 | 7/31/2006 11:52:07 AM | A | FAIL |
|
|
Min. spacing between sprinklers at the master bedroom is exceeded, spacing at the kitchen and pantry head may be incorrect if pantry wall is not installed as shown on plan, an accessible storage area not shown on plans below stairs will require protection, provide nailer plates where vertical risers pass through walls, still need to perform supply line flush, antifreeze sign to indicate type of solution required for CPVC.
|
BLD06-00239
| FIRE-Final Inspection | 7/30/2006 | 7/31/2006 | 7/31/2006 11:00:36 AM | A | PASS |
|
|
The manual flush bolts in the inactive door leaf at the doors from the classroom to the hall must be removed or provide automatic type prior to final inspection by structural, remaining life safety is acceptable.
|
FIR06-00321
| INSP-Supply line flush | 7/28/2006 | 7/31/2006 | 7/31/2006 10:11:11 AM | A | PART |
|
|
UG fire supply line flush completed satisfactory.
|
FIR06-00321
| INSP-Sprinkler Rough-in/Hydro | 7/28/2006 | 7/31/2006 | 7/31/2006 10:10:13 AM | A | PART |
|
|
Noted required corrections from previous inspection have been completed, approved plans do not show a hose supply line which has been added to two 11/2 hose valves at center columns- approved plans to reflect these modifications.
|