Inspections for the day of: Monday, July 31, 2006.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00517 FIR-Aging Inspection7/31/20067/31/20068/2/2006 1:39:08 PM DEFR
FIR05-00425 INSP-Sprinkler Rough-in/Hydro7/31/20067/31/20068/1/2006 3:46:30 PMPPART
OH rough-in at the hotel lobby drop ceiling areas as noted are okay to cover, two heads in the hard lid above reception counter do not meet min. spacing req.
FIR06-00303 INSP-Supply line flush7/31/20067/31/20068/1/2006 7:34:20 AMPPART
UG fire supply line flush performed satisfactory.
FIR06-00476 INSP-Sprinkler Rough-in7/28/20067/31/20067/31/2006 2:49:22 PMPPART
OH rough-in is okay to cover, noted two sprinkler heads in the basement which will require relocation for proper spacing and coverage.
FIR06-00394 INSP-Final Inspection7/28/20067/31/20067/31/2006 2:44:02 PMAPASS
Duct detector has been moved to an approved location, fire alarm tested satisfactory.
FIR06-00481 INSP-Final Inspection7/30/20067/31/20067/31/2006 2:19:00 PMAFAIL
One pendent head above office next to ductwork is damaged and needs to be replaced, remove plastic shipping guards from heads in 4 locations, provide missing 2nd pc canopy at 401 in restroom.
BLD06-00276 FIRE-Final Inspection7/31/20067/31/20067/31/2006 12:32:52 PMPPASS
Items on correction notice have been verified for completion, life safety passed inspection.
FIR06-00451 INSP-Sprinkler Rough-in/Hydro7/30/20067/31/20067/31/2006 11:52:07 AMAFAIL
Min. spacing between sprinklers at the master bedroom is exceeded, spacing at the kitchen and pantry head may be incorrect if pantry wall is not installed as shown on plan, an accessible storage area not shown on plans below stairs will require protection, provide nailer plates where vertical risers pass through walls, still need to perform supply line flush, antifreeze sign to indicate type of solution required for CPVC.
BLD06-00239 FIRE-Final Inspection7/30/20067/31/20067/31/2006 11:00:36 AMAPASS
The manual flush bolts in the inactive door leaf at the doors from the classroom to the hall must be removed or provide automatic type prior to final inspection by structural, remaining life safety is acceptable.
FIR06-00321 INSP-Supply line flush7/28/20067/31/20067/31/2006 10:11:11 AMAPART
UG fire supply line flush completed satisfactory.
FIR06-00321 INSP-Sprinkler Rough-in/Hydro7/28/20067/31/20067/31/2006 10:10:13 AMAPART
Noted required corrections from previous inspection have been completed, approved plans do not show a hose supply line which has been added to two 11/2 hose valves at center columns- approved plans to reflect these modifications.