ELE07-01535
| ELE-Aging Inspection | 7/31/2007 | 7/31/2007 | 8/3/2007 3:57:05 PM | | DONE |
|
|
see final
|
ELE07-02683
| Electrical Rough-In | 7/31/2007 | 7/31/2007 | 7/31/2007 3:51:41 PM | P | PASS |
|
|
john Phone #: ###-#### ri ok for kitchen, dining ceiling, front room ceiling and great room upstairs
|
ELE07-02140
| Final | 7/31/2007 | 7/31/2007 | 7/31/2007 3:27:42 PM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 7/31/2007 at 7:06:20 AM. Contact: ###-####. called contr to label panel, ok to final
|
ELE07-02171
| Final | 7/30/2007 | 7/31/2007 | 7/31/2007 2:53:12 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Joe Thomas called office to change address to Richmond St to agree with bld and physical address, ok to final
|
ELE07-02682
| Electrical Rough-In | 7/31/2007 | 7/31/2007 | 7/31/2007 2:03:08 PM | P | FAIL |
|
|
rod Phone #: ###-#### called, left message and corr notice, nec 300.4(A)&(D) edge of bored holes and raceways shall be 1 1/4" from edge of framing members, 110.22 shall identify and label garage disconnect and show off-on positions, BCC shall inspect u/g before cover- house to garage
|
ELE07-00392
| Final | 7/31/2007 | 7/31/2007 | 7/31/2007 1:04:37 PM | P | FAIL |
|
|
rod Phone #: ###-#### called, left message, left corr notice, 406.8 (B) shall use enclosure that is weatherproof whether or not plug is inserted outdoor recpt, 410.8 shall either move or abandon light fixture in upstairs closet, 422.31(B) shall provide disconnect for water heater
|
ELE07-01688
| Final | 7/27/2007 | 7/31/2007 | 7/31/2007 11:23:26 AM | A | PASS |
|
|
The builder will make sure the house is open for you. Thanks, Andrea. Phone #: ###-#### - please call for access Internet Inspection Request from: Andrea Creek called contr to flush out kitchen recpts and fix gfci for baths, ok to final
|
ELE07-01911
| Final | 7/30/2007 | 7/31/2007 | 7/31/2007 10:30:04 AM | A | PASS |
|
|
bruce - pls call 30 mins prior; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang ok to final
|
ELE07-00467
| Electrical Rough-In | 7/30/2007 | 7/31/2007 | 7/31/2007 9:25:47 AM | A | PART |
|
|
curtis - some can lights have for the waiting room are on special order so we need a partial for the rest of the walls and ceiling so the job can continue forward ; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang called contr, for 1 1/4" on smurf and mc, walls and ceilings except 6 can lites in waiting area ok to cover
|
ELE07-02017
| Final | 7/31/2007 | 7/31/2007 | 7/31/2007 8:52:08 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 7/31/2007 at 5:29:57 AM. Contact: ###-####. ok to final
|
ELE07-01786
| Final | 7/31/2007 | 7/31/2007 | 7/31/2007 8:09:29 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 7/31/2007 at 5:30:57 AM. Contact: ###-####. called, left message, 1 outlet with rev polarity , ok to final
|
ELE07-02339
| Final | 7/30/2007 | 7/31/2007 | 7/30/2007 4:25:08 PM | A | CANC |
|
|
final inspect pad C. Please call Steve Ruter Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson Inspection cancelled from web by: Kristopher Wilson
|