Inspections for the day of: Tuesday, July 31, 2007.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00377 INSP-Sprinkler Rough-in7/30/20077/31/20078/1/2007 7:24:16 PMAFAIL
See stamped plans for areas inspected and approved, circled locations for heads in need of replacement, obstructed or overspaced as noted.
FIR07-00275 INSP-Final Inspection7/30/20077/31/20077/31/2007 4:46:38 PMACANC
BLD07-00869 FIRE-Final Inspection7/30/20077/31/20077/31/2007 4:45:35 PMAPASS
Fire life safety is satisfactory, noted missing PFE to be installed today per contractor and prior to structural final.
FIR07-00560 INSP-Sprinkler Rough-in7/30/20077/31/20077/31/2007 4:18:21 PMPPART
OH install at the drop ceilings is approved for cover, noted the additional line outside the tenant space has not been added as indicated, spacing appears okay however no access was available to verify.
BLD06-00688 FIRE-Final Inspection7/30/20077/31/20077/31/2007 3:44:49 PMANR
Still pending related FA and FS permit finals.
FIR06-00704 INSP-Final Inspection7/31/20077/31/20077/31/2007 3:43:23 PMPPART
Noted items at the previous inspection have been verified for completion, remainder of system testing passed, final pending clear panel-trouble due to a SD in the elevator shaft-need to repair or replace, will sign completion forms when panel is clear.
FIR06-00728 INSP-Final Inspection7/30/20077/31/20077/31/2007 3:39:21 PMAFAIL
Overspaced heads at locations on the 2nd and 3rd floors as indicated on site.
FIR06-00934 INSP-Alarm Testing7/26/20077/31/20077/31/2007 2:18:36 PMAPASS
Fire alarm modifications passed field testing.
FIR07-00638 INSP-Sprinkler Rough-in/Hydro7/31/20077/31/20077/31/2007 12:02:05 PMPDEFR
Inspection rescheduled for 8/1 per conversation with contractor.
FIR07-00381 INSP-Sprinkler Rough-in/Hydro7/31/20077/31/20077/31/2007 12:01:14 PMAPART
OH rough-in for the TI remodel is approved for cover at the drop ceilings.
BLD06-02547 FIRE-Final Inspection7/30/20077/31/20077/31/2007 11:59:38 AMAFAIL
Missing visual indicator at the keyed locking main entry/exit door, exit sign at the south side of the office area does not function on backup power, three emergency lights in the warehouse area are not functional.
FIR07-00047 FIR-Aging Inspection7/31/20077/31/20077/31/2007 9:51:06 AM DEFR
wip