FIR07-00377
| INSP-Sprinkler Rough-in | 7/30/2007 | 7/31/2007 | 8/1/2007 7:24:16 PM | A | FAIL |
|
|
See stamped plans for areas inspected and approved, circled locations for heads in need of replacement, obstructed or overspaced as noted.
|
FIR07-00275
| INSP-Final Inspection | 7/30/2007 | 7/31/2007 | 7/31/2007 4:46:38 PM | A | CANC |
|
|
|
BLD07-00869
| FIRE-Final Inspection | 7/30/2007 | 7/31/2007 | 7/31/2007 4:45:35 PM | A | PASS |
|
|
Fire life safety is satisfactory, noted missing PFE to be installed today per contractor and prior to structural final.
|
FIR07-00560
| INSP-Sprinkler Rough-in | 7/30/2007 | 7/31/2007 | 7/31/2007 4:18:21 PM | P | PART |
|
|
OH install at the drop ceilings is approved for cover, noted the additional line outside the tenant space has not been added as indicated, spacing appears okay however no access was available to verify.
|
BLD06-00688
| FIRE-Final Inspection | 7/30/2007 | 7/31/2007 | 7/31/2007 3:44:49 PM | A | NR |
|
|
Still pending related FA and FS permit finals.
|
FIR06-00704
| INSP-Final Inspection | 7/31/2007 | 7/31/2007 | 7/31/2007 3:43:23 PM | P | PART |
|
|
Noted items at the previous inspection have been verified for completion, remainder of system testing passed, final pending clear panel-trouble due to a SD in the elevator shaft-need to repair or replace, will sign completion forms when panel is clear.
|
FIR06-00728
| INSP-Final Inspection | 7/30/2007 | 7/31/2007 | 7/31/2007 3:39:21 PM | A | FAIL |
|
|
Overspaced heads at locations on the 2nd and 3rd floors as indicated on site.
|
FIR06-00934
| INSP-Alarm Testing | 7/26/2007 | 7/31/2007 | 7/31/2007 2:18:36 PM | A | PASS |
|
|
Fire alarm modifications passed field testing.
|
FIR07-00638
| INSP-Sprinkler Rough-in/Hydro | 7/31/2007 | 7/31/2007 | 7/31/2007 12:02:05 PM | P | DEFR |
|
|
Inspection rescheduled for 8/1 per conversation with contractor.
|
FIR07-00381
| INSP-Sprinkler Rough-in/Hydro | 7/31/2007 | 7/31/2007 | 7/31/2007 12:01:14 PM | A | PART |
|
|
OH rough-in for the TI remodel is approved for cover at the drop ceilings.
|
BLD06-02547
| FIRE-Final Inspection | 7/30/2007 | 7/31/2007 | 7/31/2007 11:59:38 AM | A | FAIL |
|
|
Missing visual indicator at the keyed locking main entry/exit door, exit sign at the south side of the office area does not function on backup power, three emergency lights in the warehouse area are not functional.
|
FIR07-00047
| FIR-Aging Inspection | 7/31/2007 | 7/31/2007 | 7/31/2007 9:51:06 AM | | DEFR |
|
|
wip
|