FIR08-00359
| INSP-Final Inspection | 7/30/2008 | 7/31/2008 | 8/1/2008 4:56:11 PM | A | PASS |
|
|
Inspection passed per site visit completed by T. Cobbley.
|
FIR07-00606
| INSP-Sprinkler Rough-in | 7/30/2008 | 7/31/2008 | 7/31/2008 5:18:10 PM | P | PART |
|
|
Correction notice items regarding areas B and D plan sheet FP5 are finished, discussed balance of project to be inspected, some areas not yet ready per contractor-repairs incomplete.
|
FIR08-00255
| INSP-Final Inspection | 7/30/2008 | 7/31/2008 | 7/31/2008 5:13:34 PM | A | FAIL |
|
|
Walkthrough of classroom wings areas J,I, E and F completed today- noted items on plans in need of correction including smoke detectors to be relocated due to proximity to HVAC registers, spacing or cd adjustment at some av's, pull stations at two locations, noted minor floor plan changes, initiation devices not tested due to missing phone lines.
|
FIR07-00666
| INSP-Final Inspection | 7/28/2008 | 7/31/2008 | 7/31/2008 2:13:31 PM | A | PASS |
|
|
Fire alarm testing completed acceptable, permit finaled.
|
FIR08-00509
| INSP-Final Inspection | 7/30/2008 | 7/31/2008 | 7/31/2008 10:14:55 AM | A | PASS |
|
|
Fire alarm work passed field testing, permit finaled per TC.
|
FIR08-00508
| INSP-Final Inspection | 7/30/2008 | 7/31/2008 | 7/31/2008 10:14:02 AM | A | PASS |
|
|
Corrections verified for completion, fire alarm testing passed.
|
BLD08-01501
| FIRE-Final Inspection | 7/30/2008 | 7/31/2008 | 7/31/2008 10:12:25 AM | A | FAIL |
|
|
Need to provide one additional exit sign as discussed, per plan notes the third exit door needs to swing in the direction of travel.
|