Inspections for the day of: Thursday, July 31, 2008.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00359 INSP-Final Inspection7/30/20087/31/20088/1/2008 4:56:11 PMAPASS
Inspection passed per site visit completed by T. Cobbley.
FIR07-00606 INSP-Sprinkler Rough-in7/30/20087/31/20087/31/2008 5:18:10 PMPPART
Correction notice items regarding areas B and D plan sheet FP5 are finished, discussed balance of project to be inspected, some areas not yet ready per contractor-repairs incomplete.
FIR08-00255 INSP-Final Inspection7/30/20087/31/20087/31/2008 5:13:34 PMAFAIL
Walkthrough of classroom wings areas J,I, E and F completed today- noted items on plans in need of correction including smoke detectors to be relocated due to proximity to HVAC registers, spacing or cd adjustment at some av's, pull stations at two locations, noted minor floor plan changes, initiation devices not tested due to missing phone lines.
FIR07-00666 INSP-Final Inspection7/28/20087/31/20087/31/2008 2:13:31 PMAPASS
Fire alarm testing completed acceptable, permit finaled.
FIR08-00509 INSP-Final Inspection7/30/20087/31/20087/31/2008 10:14:55 AMAPASS
Fire alarm work passed field testing, permit finaled per TC.
FIR08-00508 INSP-Final Inspection7/30/20087/31/20087/31/2008 10:14:02 AMAPASS
Corrections verified for completion, fire alarm testing passed.
BLD08-01501 FIRE-Final Inspection7/30/20087/31/20087/31/2008 10:12:25 AMAFAIL
Need to provide one additional exit sign as discussed, per plan notes the third exit door needs to swing in the direction of travel.