Inspections for the day of: Friday, July 31, 2009.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00438 INSP-Sprinkler Rough-in/Hydro7/31/20097/31/20097/31/2009 6:24:26 PMPFAIL
One pendent head at the first floor hallway is overspaced, some heads remain yet to be replaced, remainder of permit work is acceptable, will need to schedule hydrostatic testing as discussed.
FIR09-00171 INSP-Final Inspection7/30/20097/31/20097/31/2009 6:21:18 PMAPART
Fire alarm testing for the scope of work indicated is acceptable. However, synchronization issues at the existing adjacent rooms and common exit corridors is not acceptable and will need revision prior to final approval of this permit as discussed.
FIR09-00371 INSP-Final Inspection7/30/20097/31/20097/31/2009 6:17:22 PMANR
Fire alarm testing could not be completed due to jobsite conditions blocking access to several areas.
FIR09-00033 INSP-Sprinkler Rough-in7/31/20097/31/20097/31/2009 6:15:30 PMAPART
System 14 rough-in and cover inspection completed for drop ceilings at areas as marked on stamped plan set. Noted minor modifications to floorplan and head layout okayed. One red-lined group of rooms already covered will need to be exposed for inspection as discussed.
FIR09-00033 INSP-Sprinkler Rough-in/Hydro7/24/20097/31/20097/31/2009 6:10:41 PMAPART
Completed satisfactory fire alarm testing for riser supervision at the dry goods warehouse area with the exception of the dry goods rack system currently under construction. PIV's, system control valves, flow switches tested okay, one flow switch at system #6 adjusted while on site, missing test orfice for the ESFR overhead systems also installed.
FIR09-00267 FIR-Aging Inspection7/31/20097/31/20097/31/2009 6:04:41 PM DONE
Pending site inspection for permit final.
FIR09-00411 INSP-Final Inspection7/28/20097/31/20097/30/2009 4:34:55 PMACANC
Tim Christopherson Phone #: ###-#### Internet Inspection Request from: Diane Turner Inspection cancelled from web by: Diane Turner
FIR09-00410 INSP-Final Inspection7/28/20097/31/20097/30/2009 4:34:45 PMACANC
Tim Christopherson Phone #: ###-#### Internet Inspection Request from: Diane Turner Inspection cancelled from web by: Diane Turner
FIR09-00409 INSP-Final Inspection7/28/20097/31/20097/30/2009 4:34:32 PMACANC
Tim Christopherson Phone #: ###-#### Internet Inspection Request from: Diane Turner Inspection cancelled from web by: Diane Turner