FIR12-00368
| INSP-Final Inspection | 7/23/2012 | 7/24/2012 | | A | |
|
|
call me when you get there & I will let you in. 6am Phone #: ###-#### >> Inspection requested via web by Rick Groom
|
BLD11-02317
| FIRE-Conference | 7/31/2012 | 7/31/2012 | 7/31/2012 6:41:29 PM | P | PART |
|
|
Fire life safety walkthrough for the 1st floor lobby/front counter and employee work area remodel finishes to date. Noted missing EM lights at exit discharge landings- see fire code review note #8 related. Upright sprinkler protection to be provided where drop ceilings are missing within occupied areas at the lobby. Physical barriers to be maintained between areas under construction and those accessible to building staff and the public.
|
FIR12-00033
| INSP-Alarm Testing | 7/30/2012 | 7/31/2012 | 7/31/2012 6:17:59 PM | A | PART |
|
|
Finished partial inspection for fire alarm work completed to date at the first floor lobby/front counter area including employee offices. Re-inspection for previous correction items include; MP station relocated from behind ADA partition, SD relocated from HVAC diffusers at three locations, access panels provided at dampers per IMC. Notification appliance at the foothills conference room okayed based upon adjacent coverage in the lobby through the glass partition doors. Both main lobby dampers east side to remain closed due to missing drop ceilings and area detection between phases as discussed. Audible sync issues between buildings 1 and 2 remain unchanged. 2nd floor sync issues building one to be addressed under future upgrade permits- ref. activity note 7/6. Items tested today include SD's for recall functions at both 1st floor elevators, all new SD installed to date, 3 MP's, operation at three dampers south side hall. Need to add one MP at the employee work area exit west side vestibule 102. SD at the west elevator to be relocated to the deck while drop ceilings are removed.
|
FIR12-00246
| INSP-Sprinkler Rough-in | 7/31/2012 | 7/31/2012 | 7/31/2012 5:52:09 PM | P | PART |
|
|
Overhead rough-in at the kitchen area as marked and dated on stamped plans okayed.
|
FIR11-00689
| INSP-Sprinkler Rough-in | 7/30/2012 | 7/31/2012 | 7/31/2012 5:03:25 PM | A | PART |
|
|
Verified added coverage at the stair tower lower landings, coverage adjustments to the east wall sub fab are finished.
|
BLD12-01079
| FIRE-Final Inspection | 7/31/2012 | 7/31/2012 | 7/31/2012 1:43:34 PM | P | PASS |
|
|
Fire life safety final approved.
|
BLD12-01652
| FIRE-Final Inspection | 7/31/2012 | 7/31/2012 | 7/31/2012 1:41:19 PM | P | PASS |
|
|
Fire life safety completed satisfactory.
|
FIR12-00344
| INSP-Final Inspection | 7/31/2012 | 7/31/2012 | 7/31/2012 1:38:23 PM | P | PASS |
|
|
Final walkthrough passed. Fire sprinkler permit finaled.
|
FIR12-00368
| INSP-Final Inspection | 7/30/2012 | 7/31/2012 | 7/31/2012 1:35:49 PM | A | PASS |
|
|
Inspection passed. Fire alarm permit finaled.
|
FIR12-00356
| INSP-Final Inspection | 7/30/2012 | 7/31/2012 | 7/31/2012 1:31:11 PM | A | PASS |
|
|
Fire alarm work passed field inspection. Permit finaled.
|
FIR12-00332
| INSP-Supply line flush | 7/30/2012 | 7/31/2012 | 7/31/2012 1:28:20 PM | A | PART |
|
|
UG fire supply line flush completed.
|