Inspections for the day of: Friday, July 31, 2015.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-02127 ELE-Aging Inspection7/31/20157/31/20158/6/2015 7:39:41 AM CANC
Too busy
ELE12-00814 ELE-Aging Inspection7/31/20157/31/20158/6/2015 7:39:16 AM CANC
too busy
ELE15-01196 Final7/31/20157/31/20157/31/2015 3:11:50 PMPFAIL
James is the onsite contact at ###-#### Phone #: ###-#### Inspection requested via web by Tracy Robertson 400.14- Flexible cords shall be protected from physical damage when passing through holes in covers, boxes, and similar enclosures. Asked contractor to check all installations up to date. Ranges and dryers
ELE15-01545 Final7/31/20157/31/20157/31/2015 2:56:19 PMPFAIL
James is the onsite contact at ###-#### Phone #: ###-#### Inspection requested via web by Tracy Robertson 400.14- Flexible cords shall be protected from physical damage when passing through holes in covers, boxes, and similar enclosures. Asked contractor to check all installations up to date.
ELE15-02210 Electrical Rough-In7/30/20157/31/20157/31/2015 1:28:43 PMPPASS
We are requesting a ceiling rough-in inspection for tomorrow in the afternoon. Our onsite contact is Rich @ ###-####. Thank you,
Phone #: ###-#### Inspection requested via web by Clint Tate HHO area grid rough in ok cover
ELE15-02315 Electrical Rough-In7/30/20157/31/20157/31/2015 12:46:56 PMPPASS
Contact Mike Rossknecht Phone #: ###-#### Inspection requested via web by Cathy Duchek Just finishing interior walls at this time. Basement Rough in ok cover
ELE15-02367 Temporary Service7/30/20157/31/20157/31/2015 11:29:38 AMPPASS
Phone #: ###-#### Inspection requested via web by TOM BICANDI t/s u/g n ok
ELE15-02368 Temporary Service7/30/20157/31/20157/31/2015 11:29:04 AMPPASS
Phone #: ###-#### Inspection requested via web by TOM BICANDI t/s u/g n ok
ELE15-02366 Final7/30/20157/31/20157/31/2015 11:28:20 AMAPASS
Phone #: ###-#### Inspection requested via web by TOM BICANDI Rough in under permit ELE15-01589 Final ok
ELE15-02062 Electrical Rough-In7/30/20157/31/20157/31/2015 10:43:55 AMAPASS
Phone #: ###-#### Inspection requested via web by mike brown Floor heat rough in ok cover
ELE15-02354 Permanent Service7/29/20157/31/20157/31/2015 10:22:50 AMAPASS
Dan Phone #: ###-#### Inspection requested via web by Dan Hobdey p/s o/h rec ok
ELE15-01926 Final7/30/20157/31/20157/31/2015 10:01:26 AMAFAIL
David Phone #: ###-#### 210.12- AFCI protection required on new circuits to bed. 406.11- New receptacle outlets shall be tamper resistant type
ELE15-02346 Final7/30/20157/31/20157/31/2015 9:42:00 AMAPASS
Phone #: ###-#### Inspection requested via web by steve ragan Final ok
ELE15-02349 Electrical Rough-In7/29/20157/31/20157/31/2015 9:27:30 AMAPASS
underground // Joel Phone #: ###-#### Future underground communication conduits and underground for portable classroom rough in ok cover
ELE15-02351 Temporary Service7/30/20157/31/20157/31/2015 9:02:16 AMAPASS
Phone #: ###-#### Inspection requested via web by Rowdy Monroe t/s u/g n ok
ELE15-02212 Temporary Service7/31/20157/31/20157/31/2015 8:51:15 AMAPASS
sorry for wasting your time...all fixed now...Tom Phone #: ###-#### Inspection requested via web by Bob Glenn t/s u/g n ok
ELE15-02306 Rough-In Permanent Service7/31/20157/31/20157/31/2015 8:48:15 AMPPASS
ready now Phone #: ###-#### Inspection requested via web by Bob Glenn Rough in ok cover p/s u/g n ok