ELE17-01511
| Electrical Rough-In | 7/31/2017 | 7/31/2017 | 7/31/2017 2:03:29 PM | P | PASS |
|
|
Ceiling grid inspection Phone #: ###-#### Inspection requested via web by Barbara Szurgot Grid rough in ok cover
|
ELE17-01990
| Final | 7/30/2017 | 7/31/2017 | 7/31/2017 1:35:47 PM | A | PASS |
|
|
Late AM please Phone #: ###-#### Inspection requested via web by Jim Williams Final ok
|
ELE13-01291
| Final | 7/28/2017 | 7/31/2017 | 7/31/2017 1:11:05 PM | A | FAIL |
|
|
Walk down fountain controls and spiral slide on exterior of building. Phone #: ###-#### Inspection requested via web by Tom Betty 110.3- Shall verify listing of spiral slide and components. Found listing for control cabinet, verify if all are part of same listing. 680.26(B)(2)- Although water feature does not meet the definition of a pool, AHJ shall require bonding of perimeter surfaces and equipment associated due to wet concrete in area of foggers. If accessible #8 solid continue to equipment from shells as inspected in June of 2016 and shall include electrical equipment discribed in 680.26(B)(6). 400.17- Power supply cord entering control cabinet shall be protected from physical damage where it enters or be relocated to interior.
|
ELE17-02111
| Rough-In Permanent Service | 7/28/2017 | 7/31/2017 | 7/31/2017 9:29:31 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Rowdy Monroe Rough in ok cover p/s u/g n ok
|
ELE17-02439
| Rough-In Permanent Service | 7/30/2017 | 7/31/2017 | 7/31/2017 8:56:29 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Ben Archibald Rough in ok cover p/s u/g n ok
|
ELE17-02435
| Conference | 7/28/2017 | 7/31/2017 | 7/28/2017 12:00:00 AM | A | CANC |
|
|
I''d like to have a consultation before beginning work on my 18x24 garage/shop Phone #: ###-#### >> Inspection requested via web by Dennis Ahern-cancelled until we hear from the customer about fees-left message on his phone
|