Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC18-03675 Rough-in7/31/20187/31/20187/31/2018 4:09:35 PMPFAIL
- B vent for furnace needs 1" clearances in the crawl space, main floor in the closet where in goes into the wall, and i need to see an insulation sheild in the attic
-Main supply trunk in the crawl is laying on the ground and has the B vent laying on it- supply branches need dampers for air balancing and supply boots sealed
- need service dissconnect for the furnace in the crawl space and a light - need to know where the crawl access is going to be and how big it is going to be for removal of equipment if needed
- Line set insulation needs fixed and UV tape- penetration out the foundation needs to be sealed and the breaker size is too large- power whip to A/C needs to be weather tight
- range hood vent is not tied into termination properly
- need to see that the permit has exhaust fans, range hood,and duct work added and fees paid
- Man J. needs to be performed and approved by the city of boise
MEC18-03745 Final7/31/20187/31/20187/31/2018 3:40:37 PMPPASS
Please call on way: Tyrel ###-#### Phone #: ###-#### Inspection requested via web by Krista Boss- RTU # 3 final ok
MEC18-03663 Rough-in7/31/20187/31/20187/31/2018 3:21:22 PMPPASS
Pressure test and Rough in Please call ahed for lock box code // Eddie Phone #: ###-####
fireplace R/I ok- 20lb gas pressure test ok
MEC17-02479 Mec-Aging Inspection7/31/20187/31/20187/31/2018 2:58:00 PM CANC
MEC18-03675 Rough-in7/30/20187/31/20187/31/2018 2:13:11 PMPFAIL
vacant, call for access code - Steve Phone #: ###-####- no access called steve and left message
MEC18-03150 Final7/30/20187/31/20187/31/2018 2:08:02 PMPPASS
**** same customer as permit # MEC18-03096. Would like this inspection first. Please call Wendy 30 min prior to arrival. Phone #: ###-#### Inspection requested via web by Andrea
Grigsby
- furnace ac coil ok
MEC18-03096 Final7/30/20187/31/20187/31/2018 1:53:40 PMPPASS
*** same customer as MEC18-03150. They would like 3316 Bridgecourt inspected first please. Please call Wendy 30 min prior to arrival. Phone #: ###-#### Inspection requested
via web by Andrea Grigsby
- furnace ac coil co ok
MEC18-03719 Final7/30/20187/31/20187/31/2018 1:16:58 PMPPASS
Please call Kyle to ensure install is complete. Thank you! ###-#### Phone #: ###-#### Inspection requested via web by Rick Borg
- A/C coil co ok
MEC17-04966 Mec-Aging Inspection7/31/20187/31/20187/31/2018 1:05:04 PM DONE
called contractor to schedule inspection with homeowner
MEC17-04978 Mec-Aging Inspection7/31/20187/31/20187/31/2018 1:01:35 PM DONE
called contractor about scheduling inspection but no answered left a message
MEC18-03653 Final7/26/20187/31/20187/31/2018 11:29:06 AMAPASS
Call Barbara at ###-#### to coordinate Phone #: ###-#### Inspection requested via web by Sabrina DeHority- furnace ac coil co ok
MEC18-03592 Final7/30/20187/31/20187/31/2018 11:00:25 AMAFAIL
Please inspect about 10 AM if possible and call Raymond Hansen prior to inspection. ###-####. Phone #: ###-#### Inspection requested via web by Mary LaFayette- need a 90 on the condensate turned down- ac coil co ok
MEC18-03665 Rough-in7/31/20187/31/20187/31/2018 10:35:42 AMAPASS
Inspection requested via web by Floyd Floyd Peek- water heater flue ok- R/I ok - 20lb gas pressure test ok- 5lb flue pressure ok
MEC18-02476 Rough-in7/30/20187/31/20187/31/2018 10:16:16 AMAPART
Please Re-inspect 104-204-303-304 . thanks Phone #: ###-#### Inspection requested via web by Gary Reeves- R/I ok
MEC18-03598 Pressure Test7/30/20187/31/20187/31/2018 10:07:10 AMAPASS
Phone #: ###-#### Inspection requested via web by Chris Field- 20lb gas pressure test ok
MEC18-03663 Rough-in7/26/20187/31/20187/31/2018 10:05:42 AMANH
Phone #: ###-#### Inspection requested via web by Brian Preece- no access needed a code lock box
MEC18-03663 Pressure Test7/26/20187/31/20187/31/2018 10:04:49 AMANH
Phone #: ###-#### Inspection requested via web by Brian Preece- no access
MEC18-03743 Final7/30/20187/31/20187/31/2018 9:41:13 AMAPASS
Call customer to meet you a the house /jobsite. Thanks
if any other questions Call Tim ###-#### Phone #: ###-#### Inspection requested via web by Rene Neumeyer- final ok
MEC18-03743 Rough-in7/30/20187/31/20187/31/2018 9:40:51 AMAPASS
Call customer to meet you a the house /jobsite. Thanks
if any other questions Call Tim ###-#### Phone #: ###-#### Inspection requested via web by Rene Neumeyer- clearances ok -R/I ok
MEC18-02222 Final7/30/20187/31/20187/31/2018 9:02:55 AMACANC
(gas/range)- Johnny Phone #: ###-####
should have been a R/I for the range- i also need to see a 5lb flue test on upstairs furnace still
MEC18-02222 Rough-in7/31/20187/31/20187/31/2018 9:02:19 AMPPASS
(gas/range)- Johnny Phone #: ###-####
R/I ok on range