Inspections for the day of: Wednesday, July 31, 2019.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-02503 Final7/30/20197/31/20197/31/2019 2:38:26 PMPPASS
Phone #: ###-#### Inspection requested via web by michael hunt Final ok
ELE19-02503 Electrical Rough-In7/31/20197/31/20197/31/2019 2:19:00 PMPPASS
Phone #: ###-#### Inspection requested via web by michael hunt
Frid rough in ok cover
ELE19-02670 Final7/31/20197/31/20197/31/2019 1:57:00 PMPPASS
Phone #: ###-#### Inspection requested via web by Steven Ragan Final ok
ELE19-01088 Final7/30/20197/31/20197/31/2019 1:02:18 PMPFAIL
Phone #: ###-#### Inspection requested via web by Kevin Perez
Corrections not complete.
110.22(A)- AC disconnecting means shall be identified as to which AC unit is controlled by which disconnect.
408.4- Panel 2 circuit directory not complete.
ELE19-02503 Electrical Rough-In7/30/20197/31/20197/31/2019 11:21:04 AMAFAIL
grid inspection Phone #: ###-#### Inspection requested via web by michael hunt
300.11- Luminaires shall be supported independant of grid. Track lts.
314.24- Boxes shall be secured in place. Discplay table.
ELE19-02438 Rough-In Permanent Service7/30/20197/31/20197/31/2019 10:36:15 AMAFAIL
Phone #: ###-#### Inspection requested via web by Hidajet Zahic
250.24- AC service shall have grounded conductor bonded to a grounding electrode system described in 250.52. No GEC or grounding electrode found.
300.4- Nail plates needed in master bed and family room marked with X.
314.25- Recessed can over master shower shall have junction box cover installed to completely cover opening.
330.12- MC and NM cables shall not be installed where subject to damage. Cut corner at top of north wall.
330.30- Secure and support MC for mini split systems.
ELE19-02829 Permanent Service7/30/20197/31/20197/31/2019 10:05:40 AMAFAIL
Contact: Mike Mulvahill.... street light service inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden
110.24- Available fault current shall be posted prior to other than residential permanent service inspection. 10K rated main
Ground rods were attempted to drive vertical, then layed down to 45 degrees and bent over at top. Verbal notice
ELE19-02695 Rough-In Permanent Service7/30/20197/31/20197/31/2019 9:23:43 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn
Furnace in attic all boxes trimmed out.
Rough in ok cover p/s u/g n ok