ELE19-02503
| Final | 7/30/2019 | 7/31/2019 | 7/31/2019 2:38:26 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by michael hunt Final ok
|
ELE19-02503
| Electrical Rough-In | 7/31/2019 | 7/31/2019 | 7/31/2019 2:19:00 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by michael hunt Frid rough in ok cover
|
ELE19-02670
| Final | 7/31/2019 | 7/31/2019 | 7/31/2019 1:57:00 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Steven Ragan Final ok
|
ELE19-01088
| Final | 7/30/2019 | 7/31/2019 | 7/31/2019 1:02:18 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Kevin Perez Corrections not complete. 110.22(A)- AC disconnecting means shall be identified as to which AC unit is controlled by which disconnect. 408.4- Panel 2 circuit directory not complete.
|
ELE19-02503
| Electrical Rough-In | 7/30/2019 | 7/31/2019 | 7/31/2019 11:21:04 AM | A | FAIL |
|
|
grid inspection Phone #: ###-#### Inspection requested via web by michael hunt 300.11- Luminaires shall be supported independant of grid. Track lts. 314.24- Boxes shall be secured in place. Discplay table.
|
ELE19-02438
| Rough-In Permanent Service | 7/30/2019 | 7/31/2019 | 7/31/2019 10:36:15 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Hidajet Zahic 250.24- AC service shall have grounded conductor bonded to a grounding electrode system described in 250.52. No GEC or grounding electrode found. 300.4- Nail plates needed in master bed and family room marked with X. 314.25- Recessed can over master shower shall have junction box cover installed to completely cover opening. 330.12- MC and NM cables shall not be installed where subject to damage. Cut corner at top of north wall. 330.30- Secure and support MC for mini split systems.
|
ELE19-02829
| Permanent Service | 7/30/2019 | 7/31/2019 | 7/31/2019 10:05:40 AM | A | FAIL |
|
|
Contact: Mike Mulvahill.... street light service inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden 110.24- Available fault current shall be posted prior to other than residential permanent service inspection. 10K rated main Ground rods were attempted to drive vertical, then layed down to 45 degrees and bent over at top. Verbal notice
|
ELE19-02695
| Rough-In Permanent Service | 7/30/2019 | 7/31/2019 | 7/31/2019 9:23:43 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn Furnace in attic all boxes trimmed out. Rough in ok cover p/s u/g n ok
|