Inspections for the day of: Thursday, July 5, 2001.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorAlan Hauser
TitleMEC-COM/RES INSPECTOR
Phone #794-9453
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC01-00956 MEC-Aging Inspection7/5/20017/5/20017/5/2001 12:00:00 AM CANC
MEC01-00618 Final7/3/20017/5/20017/5/2001 12:00:00 AMAPASS
###-####
MEC01-01863 Final7/3/20017/5/20017/5/2001 12:00:00 AMAPASS
###-#### mike
MEC01-01326 Rough-in7/3/20017/5/20017/5/2001 12:00:00 AMACANC
done by #411 7/5/2001 10:42:29 AM
MEC01-01888 Final7/3/20017/5/20017/5/2001 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 07/03/2001 at 16:11:03. Contact: ###-####.
MEC01-01768 Rough-in7/4/20017/5/20017/5/2001 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 07/04/2001 at 12:19:27. Contact: ###-####.
MEC01-01769 Rough-in7/4/20017/5/20017/5/2001 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 07/04/2001 at 12:20:22. Contact: ###-####.
MEC01-00776 Pressure Test7/3/20017/5/20017/5/2001 12:00:00 AMAFAIL
c/n posted at front trailer 7/5/2001 9:55:24 AM
MEC01-01544 Final7/3/20017/5/20017/5/2001 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 07/03/2001 at 12:10:14. Contact: ###-####.
MEC01-00763 Pressure Test7/5/20017/5/20017/5/2001 12:00:00 AMPFAIL
one test 20# for two furnaces pasted, one 20# for heaters failed, and mainline test gage bad, back plate bent and wouldn't let needle move as air was let out. 7/5/2001 1:31:52 PMat 12:30 pressure was on 58#, told to pump up and would come back, at 1:15 looked at gage and back plate was bent to hold needle. talked to henry, and request new inspection 7/5/2001 1:33:55 PM
MEC01-01168 Final7/5/20017/5/20017/5/2001 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 07/05/2001 at 07:36:52. Contact: ###-####.
MEC01-01394 Rough-in7/5/20017/5/20017/5/2001 12:00:00 AMPFAIL
solid fuel fireplace has been dropped with casing crushed and interior fire box liner cracked from front to back, called contractor to have it looked at to see if it can be repaired after sheetrocked, if not needs replaced 7/5/2001 2:16:42 PM
MEC01-01394 Rough-in7/5/20017/5/20017/5/2001 12:00:00 AMPPASS
Added by Inspector: 350 On 7/5/2001 2:28:04 PM fireplace contractor called, said broken firebox liners were on order, will check on final for new liners