FIR05-00072
| FIR-Aging Inspection | 7/5/2005 | 7/5/2005 | 7/7/2005 1:44:18 PM | | NR |
|
|
Per Jason work is in progress
|
BLD04-01519
| FIRE-Final Inspection | 7/5/2005 | 7/5/2005 | 7/5/2005 3:40:01 PM | P | PASS |
|
|
Fire life safety finaled
|
BLD04-01518
| FIRE-Final Inspection | 7/5/2005 | 7/5/2005 | 7/5/2005 3:39:38 PM | P | PASS |
|
|
Life safety finaled
|
FIR05-00274
| INSP-Sprinkler Rough-in/Hydro | 7/5/2005 | 7/5/2005 | 7/5/2005 11:52:19 AM | P | PART |
|
|
Retaining strap over men's restroom needs bent around truss and plans indicate 200 degree heads to be used but 155 have been used everywhere except they are mixed in the office and in the women's restroom. Piping is ok to cover
|