ELE06-01159
| ELE-Aging Inspection | 7/5/2006 | 7/5/2006 | 7/5/2006 4:59:12 PM | | DONE |
|
|
see final
|
ELE06-01159
| Final | 7/5/2006 | 7/5/2006 | 7/5/2006 4:58:50 PM | P | PASS |
|
|
looked at sign, ok to final
|
ELE06-01746
| Final | 7/5/2006 | 7/5/2006 | 7/5/2006 4:56:33 PM | P | FAIL |
|
|
allan - suite 90; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called, left message, left corr notice, nec 348.30 fmc shall be supported within 12" of box,358.30(A) emt shall be supported within 3' of box, 408.4 circuit directory shall be clear and concise for every circuit, 110.12(A) unused openings in boxes shall be closed,725.3(B) abandoned cl2, cl3, and pltc shall be removed,314.25 each box shall have a cover, 300.11(B) raceways shall not be used as support for other cables BCC no violations shall be retained
|
ELE06-01710
| Conference | 7/3/2006 | 7/5/2006 | 7/5/2006 4:13:30 PM | P | DONE |
|
|
ADAM; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles talked about panel and using existing while ri being done and then putting in new service later
|
ELE06-02198
| Permanent Service | 7/5/2006 | 7/5/2006 | 7/5/2006 3:27:39 PM | P | PASS |
|
|
brandon ###-#### p/s u/g n ok unit on 3oth st only
|
ELE06-02348
| Temporary Service | 7/5/2006 | 7/5/2006 | 7/5/2006 1:42:20 PM | P | FAIL |
|
|
Tom; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt called contr, left corr notice, nec 312.5 all conductors entering enclosure shall have abrasion protection,BCC address shall be posted, job id sticker shall be posted
|
ELE06-00671
| Electrical Rough-In | 7/5/2006 | 7/5/2006 | 7/5/2006 1:26:16 PM | P | PASS |
|
|
tye - underground; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok to cover gec north side mcc area
|
ELE06-01152
| Electrical Rough-In | 7/3/2006 | 7/5/2006 | 7/5/2006 9:30:13 AM | A | PASS |
|
|
richard; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ric ok
|