ELE07-02313
| Electrical Rough-In | 7/5/2007 | 7/5/2007 | 7/5/2007 3:20:50 PM | P | PASS |
|
|
Electrician is Tony Norton, please inspect grounding electrode and code corrections Phone #: ###-#### Internet Inspection Request from: Jarrod Clymerr/i ok corr. made, electrode ok for concrete cover only
|
ELE07-02313
| Permanent Service | 7/5/2007 | 7/5/2007 | 7/5/2007 3:19:05 PM | P | PASS |
|
|
Electrician is Tony Norton, please inspect grounding electrode and code corrections Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer p/s o/h rec. ok
|
ELE07-01641
| Permanent Service | 7/5/2007 | 7/5/2007 | 7/5/2007 3:02:30 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: jesse busack p/s u/g new ok
|
ELE07-02387
| Temporary Service | 7/5/2007 | 7/5/2007 | 7/5/2007 2:12:48 PM | P | PASS |
|
|
chris; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang t/s o/h new ok
|
ELE07-00988
| Final | 7/4/2007 | 7/5/2007 | 7/5/2007 1:47:36 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Erick Baker ok
|
ELE07-02323
| Electrical Rough-In | 7/3/2007 | 7/5/2007 | 7/5/2007 1:19:48 PM | P | PART |
|
|
Cancle prior inspection made for thurs Am and change to thursday Pm Bonding inspection. Thank you Phone #: ###-#### Internet Inspection Request from: Jari Rivers pool bond only ok
|
ELE07-02381
| Rough-In Permanent Service | 7/5/2007 | 7/5/2007 | 7/5/2007 12:39:38 PM | P | FAIL |
|
|
clay Phone #: ###-#### corr. posted met contr, 250.52(A)(1)or 104(A)(1) grd or bond water system, install 2 grd rods house, bond EMT out of meter, address range and dryer, 4 wire recpts and pigtails, BBC u/g from house to garage installed by general contr, no permit covered without inspection
|
ELE07-01810
| Final | 7/3/2007 | 7/5/2007 | 7/5/2007 9:56:55 AM | A | PASS |
|
|
dan; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang ok
|
ELE07-02378
| Electrical Rough-In | 7/3/2007 | 7/5/2007 | 7/5/2007 9:16:15 AM | A | PASS |
|
|
greg Phone #: ###-#### ok
|
ELE07-02323
| Electrical Rough-In | 6/29/2007 | 7/5/2007 | 7/5/2007 8:33:26 AM | A | CANC |
|
|
bonding inspection on swimming pool for thursday July 5, Phone #: ###-#### Internet Inspection Request from: Jari Rivers
|
ELE07-01741
| Final | 7/5/2007 | 7/5/2007 | 7/5/2007 8:32:39 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 7/5/2007 at 6:20:13 AM. Contact: ###-####. ok
|