FIR06-00940
| INSP-Sprinkler Rough-in | 7/3/2007 | 7/5/2007 | 7/5/2007 5:16:39 PM | A | FAIL |
|
|
Inspection intended for FIR07-00205, inspected areas C and D on the 2nd level, see sheet FP8 for defficiencies including overspaced heads and blocked heads.
|
FIR07-00203
| INSP-Sprinkler Rough-in/Hydro | 7/5/2007 | 7/5/2007 | 7/5/2007 3:33:20 PM | P | DEFR |
|
|
Scheduled by a contractor via Hello! on 7/5/2007 at 7:31:03 AM. Contact: ###-####.
|
FIR07-00034
| INSP-Final Inspection | 7/3/2007 | 7/5/2007 | 7/5/2007 3:27:27 PM | A | PASS |
|
|
Shell fire sprinkler permit is approved for final as noted.
|
FIR07-00542
| INSP-Final Inspection | 7/5/2007 | 7/5/2007 | 7/5/2007 2:48:30 PM | P | PASS |
|
|
Fire alarm work passed field inspection, permit finaled.
|
BLD06-02700
| FIRE-Final Inspection | 7/5/2007 | 7/5/2007 | 7/5/2007 2:47:24 PM | P | FAIL |
|
|
Emergency light at the elevator lobby 5th floor failed to function, one fire door at the 3rd floor west side atrium pair failed to close on general alarm, exit sign at the 2nd floor east side does not illuminate on power fail.
|
BLD06-02700
| FIRE-Sprinkler Rough-in | 7/5/2007 | 7/5/2007 | 7/5/2007 2:44:07 PM | P | PASS |
|
|
Required corrections for the corridor fire sprinklers on the 2nd, 3rd, 4th, and 5th levels completed satisfactory.
|
FIR07-00234
| INSP-Sprinkler Rough-in/Hydro | 7/3/2007 | 7/5/2007 | 7/5/2007 1:44:22 PM | P | FAIL |
|
|
OH rough-in is not approved for cover until system piping is correctly attatched to the structure as required, missing hangers and upward restraint at several locations, noted some heads have been added and piping relocated from approved plan set, OH hydro test not ready at this time due to pressure loss, tenting appears adequate.
|
FIR07-00203
| INSP-Sprinkler Rough-in/Hydro | 7/3/2007 | 7/5/2007 | 7/5/2007 12:44:33 PM | A | PART |
|
|
Begin retest of the 24 hr. pneumatic for the roof level dry system at 12:30 pm with 44 1/2 psi at the guage.
|
FIR06-01010
| INSP-Final Inspection | 7/3/2007 | 7/5/2007 | 7/5/2007 11:21:49 AM | A | PASS |
|
|
UG fire supply line permit finaled.
|
FIR07-00543
| INSP-Sprinkler Rough-in/Hydro | 7/3/2007 | 7/5/2007 | 7/3/2007 4:24:49 PM | A | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: John Warnick Inspection cancelled from web by: John Warnick
|