Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-01403 Final6/30/20177/5/20177/5/2017 2:48:26 PMPPASS
Phone #: ###-#### Inspection requested via web by Dan Surerus Final ok
ELE17-01367 Electrical Rough-In7/5/20177/5/20177/5/2017 2:31:38 PMPPASS
We need an underground in floor inspection for the east half of the building. Thank you. Phone #: ###-#### Inspection requested via web by Tom Jenkins
Seperate electrical permits required for each buillding permit. Pool, hotel.
East 1/2 underfloor underground rough in ok cover
ELE16-01134 Electrical Rough-In7/5/20177/5/20177/5/2017 1:56:31 PMPPASS
We are requesting a rough-in inspection for level 4 and level 7 kind bedrooms and the linen chute shaft. Our contact is Bobby @ ###-####. Thank you, Phone #: ###-#### Inspection requested via web by Clint Tate
Discussed level 1 N. E. mechenical room work space for 3 disconnects. Minimum work space shall be provided. They will most likely be installed facing door.
2 rooms noted 4th and 7th king rooms only wall rough in ok cover
MIS17-00210 ELE-Conference7/3/20177/5/20177/5/2017 11:44:41 AMANH
complaint electrical work without permit, energized shed
Unable to make contact. Scheduled retry
7-6-17
ELE17-01174 Final7/4/20177/5/20177/5/2017 11:30:47 AMAPASS
Both corrections have been completed. Garage code is 1069 Phone #: ###-#### Inspection requested via web by Clay Jackson
Correction done. Final ok
ELE17-02088 Electrical Rough-In7/3/20177/5/20177/5/2017 11:13:24 AMAFAIL
We are requesting a wall rough-in inspection for Wednesday July 5th in the morning. Our contact is Mike @ ###-####. Thank you Phone #: ###-#### Inspection requested via web by Clint Tate
300.4- MC cable shall be protected from physical damage where run thru holes that do not maintain 1 1/4" from framing surface.
330.12- MC shall not be installed where subject to physical damage. Secure in stud bay and not in channel of studs.
330.30- MC shall be secured with in 12" of a box. 3 locations.
Called contact and had verbal correction.
ELE17-02025 Rough-In Permanent Service7/4/20177/5/20177/5/2017 10:41:01 AMAFAIL
Phone #: ###-#### Inspection requested via web by Bob Glenn
110.3- Fireplace igniter wire shall be secured as to not be in contact with fireplace shell as per manufacurers instructions.
210.52- Tech room receptacle outlet shall be added to serve wall space with in 6' of left side of door.
210.52- Up family room shall have receptacle outlets added to serve wall space created by rail.
800.24- Communication wires shal be installed in a manner so they are not subject to physical damage. Upstairs hanging below ceiling.
ELE17-02104 Temporary Service7/3/20177/5/20177/5/2017 9:28:25 AMAPASS
I have that this property is 87/1 not 0/1. Phone #: ###-#### Inspection requested via web by Darryn Coburn
t/s u/g n ok
ELE17-02100 Conference7/3/20177/5/20177/5/2017 8:51:48 AMACANC
Chris Phone #: ###-####
Owner called Daryl D. to inform job not ready and would like to cancel. Done