ELE17-01403
| Final | 6/30/2017 | 7/5/2017 | 7/5/2017 2:48:26 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Dan Surerus Final ok
|
ELE17-01367
| Electrical Rough-In | 7/5/2017 | 7/5/2017 | 7/5/2017 2:31:38 PM | P | PASS |
|
|
We need an underground in floor inspection for the east half of the building. Thank you. Phone #: ###-#### Inspection requested via web by Tom Jenkins Seperate electrical permits required for each buillding permit. Pool, hotel. East 1/2 underfloor underground rough in ok cover
|
ELE16-01134
| Electrical Rough-In | 7/5/2017 | 7/5/2017 | 7/5/2017 1:56:31 PM | P | PASS |
|
|
We are requesting a rough-in inspection for level 4 and level 7 kind bedrooms and the linen chute shaft. Our contact is Bobby @ ###-####. Thank you, Phone #: ###-#### Inspection requested via web by Clint Tate Discussed level 1 N. E. mechenical room work space for 3 disconnects. Minimum work space shall be provided. They will most likely be installed facing door. 2 rooms noted 4th and 7th king rooms only wall rough in ok cover
|
MIS17-00210
| ELE-Conference | 7/3/2017 | 7/5/2017 | 7/5/2017 11:44:41 AM | A | NH |
|
|
complaint electrical work without permit, energized shed Unable to make contact. Scheduled retry 7-6-17
|
ELE17-01174
| Final | 7/4/2017 | 7/5/2017 | 7/5/2017 11:30:47 AM | A | PASS |
|
|
Both corrections have been completed. Garage code is 1069 Phone #: ###-#### Inspection requested via web by Clay Jackson Correction done. Final ok
|
ELE17-02088
| Electrical Rough-In | 7/3/2017 | 7/5/2017 | 7/5/2017 11:13:24 AM | A | FAIL |
|
|
We are requesting a wall rough-in inspection for Wednesday July 5th in the morning. Our contact is Mike @ ###-####. Thank you Phone #: ###-#### Inspection requested via web by Clint Tate 300.4- MC cable shall be protected from physical damage where run thru holes that do not maintain 1 1/4" from framing surface. 330.12- MC shall not be installed where subject to physical damage. Secure in stud bay and not in channel of studs. 330.30- MC shall be secured with in 12" of a box. 3 locations. Called contact and had verbal correction.
|
ELE17-02025
| Rough-In Permanent Service | 7/4/2017 | 7/5/2017 | 7/5/2017 10:41:01 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn 110.3- Fireplace igniter wire shall be secured as to not be in contact with fireplace shell as per manufacurers instructions. 210.52- Tech room receptacle outlet shall be added to serve wall space with in 6' of left side of door. 210.52- Up family room shall have receptacle outlets added to serve wall space created by rail. 800.24- Communication wires shal be installed in a manner so they are not subject to physical damage. Upstairs hanging below ceiling.
|
ELE17-02104
| Temporary Service | 7/3/2017 | 7/5/2017 | 7/5/2017 9:28:25 AM | A | PASS |
|
|
I have that this property is 87/1 not 0/1. Phone #: ###-#### Inspection requested via web by Darryn Coburn t/s u/g n ok
|
ELE17-02100
| Conference | 7/3/2017 | 7/5/2017 | 7/5/2017 8:51:48 AM | A | CANC |
|
|
Chris Phone #: ###-#### Owner called Daryl D. to inform job not ready and would like to cancel. Done
|