BLD16-03176
| FIRE-Final Inspection | 7/3/2017 | 7/5/2017 | 7/5/2017 2:12:05 PM | P | FAIL |
|
|
Still missing two exit signs as marked on the city approved plans.
|
FIR16-00821
| INSP-Sprinkler Rough-in | 7/3/2017 | 7/5/2017 | 7/5/2017 2:11:18 PM | P | FAIL |
|
|
Contact plan review about plan modifications due to additional 90's in the 1 1/2" branchlines that effect the hydraulic calculations. Three branchlines need to be modified for spacing in the trusses and insulation needs to be added in the combustible concealed spaces as discussed. I also noted potential obstructions to the side wall sprinkler heads due to light fixtures. Piping can not be covered yet.
|
BLD17-00818
| FIRE-Final Inspection | 7/5/2017 | 7/5/2017 | 7/5/2017 10:42:23 AM | P | PASS |
|
|
life safety passed
|
FIR17-00080
| INSP-Sprinkler Rough-in/Hydro | 6/30/2017 | 7/5/2017 | 7/5/2017 10:11:33 AM | A | PASS |
|
|
System #1 and #2 overhead hydro tests passed
|
FIR16-00284
| INSP-Sprinkler Rough-in | 7/5/2017 | 7/5/2017 | 7/5/2017 9:58:45 AM | P | PASS |
|
|
Second floor cover for the soffits is ok for cover in the corridor.
|
BLD17-00302
| FIRE-Conference | 7/3/2017 | 7/5/2017 | 7/5/2017 9:27:44 AM | A | DONE |
|
|
Mark and I discussed the removal of an old sprinkler system in the basement. I deferred him to a demo permit. The existing system consists of two upright heads in the mechanical room with a flow switch, alarm bell in the room and a quarter turn valve locked open. The 1" piping is fed from a 3/4" feed. I could not find any old permits for this work and there are no annual inspection tags.
|