Inspections for the day of: Thursday, July 5, 2018.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-02082 Electrical Rough-In6/29/20187/5/20187/5/2018 2:34:55 PMPPASS
Richard---new meter based panel upgrade Phone #: ###-####
p/s u/g rec ok
ELE18-01610 Final7/5/20187/5/20187/5/2018 1:58:55 PMPPASS
Door code is 9876 if needed Phone #: ###-#### Inspection requested via web by Ron Zimmerman Final ok
ELE18-01909 Final7/3/20187/5/20187/5/2018 11:35:12 AMANH
Chad VanOrden is contact at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce
All doors locked and posted no entry with out badge. Unable to contact anyone for access. Recall when available.
ELE18-01979 Final7/3/20187/5/20187/5/2018 11:14:23 AMAPASS
Homeowner: Tim Grissom - 2084015254 Phone #: ###-#### Inspection requested via web by BRS Permitting
Final ok
ELE17-04116 Electrical Rough-In7/3/20187/5/20187/5/2018 10:38:11 AMAPASS
Please inspect floor heat install in His master bath and Her master bath. Phone #: ###-#### Inspection requested via web by ERIC CENTERS
Both master bathrooms floor heat rough in ok cover
ELE18-01352 Final7/4/20187/5/20187/5/2018 10:37:35 AMAFAIL
Garage code 3283 Phone #: ###-#### Inspection requested via web by William Andrews
110.3- Devices shall be wired as per manufacturers instructions. Reverse polarity at 2 locations in master bed.
210.8- Receptacles located with in 6' of a sink shall have GFCI protection. up rec rm. 210.52- Area each side of fireplace concidered wall space. Shall have a receptacle outlet located with in 6' of fireplace.
ELE18-02176 Temporary Service7/3/20187/5/20187/5/2018 9:05:03 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk
t/s u/g n ok
ELE18-01889 Electrical Rough-In7/3/20187/5/20187/5/2018 8:33:39 AMAPASS
UFER Underground Inspection. Steve Hook is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce
Discussed the need for an electrical permit for each BLD permit. 1 permit for gym, kitchen ect. and 1 permit for chapel and daycare. Contact to call and confirm permit issues. Concrete encased electrode on west side rough in ok cover