Inspections for the day of: Thursday, July 5, 2018.
Number of inspections: 20
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBrian Scoles
TitleMEC INSPECTOR
Phone #914-4915
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC18-03161 Final7/5/20187/5/20187/5/2018 3:55:08 PMPPASS
mini split final ok
MEC18-03162 Final7/5/20187/5/20187/5/2018 3:22:02 PMPPASS
Would like later PM and call when on way. Thank you! Phone #: ###-#### Inspection requested via web by Xanti Berria- a/c coil co ok
MEC18-02916 Final6/28/20187/5/20187/5/2018 2:44:14 PMPPASS
Please call Kyle to ensure install is complete. Thank you! ###-#### Phone #: ###-#### Inspection requested via web by Rick Borg- a/c coil co ok
MEC18-03066 Final6/28/20187/5/20187/5/2018 2:22:55 PMPPASS
INSTALLER JAROD ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- 2 RTU's ok- economizer drain ducting sealed ok
MEC18-01647 Final7/5/20187/5/20187/5/2018 1:26:11 PMPPASS
pls call so can meet at job site Phone #: ###-#### Inspection requested via web by Dave Sorensen- final ok
MEC18-02968 Final7/3/20187/5/20187/5/2018 11:31:02 AMAPASS
LATE AM INSPECTION IF POSSIBLE PLEASE. HOMEOWNER WILL BE HOME FROM 11:00 AM TO 2:00 PM. PLEASE LET ME KNOW IF THERE ARE ANY ISSUES WITH THIS. THANK YOU! Phone #: ###-#### Inspection requested via web by Aaron Alandt- furnace a/c coil co ok
MEC18-03135 Final7/5/20187/5/20187/5/2018 11:13:23 AMPCANC
Please call Donald Clayton prior to inspection at ###-#### Phone #: ###-#### >> Inspection requested via web by Mary LaFayette Inspection cancelled from web by: Mary LaFayette
MEC18-03151 Pressure Test7/3/20187/5/20187/5/2018 10:08:18 AMAFAIL
if questions call Jerry @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann- gauge at fireplace below 20psi- tried to call Jerry no answer
MEC18-01905 Final7/3/20187/5/20187/5/2018 9:34:22 AMAFAIL
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN- need sediment trap between shut off valve and appliances(furnace and water heater) per G2419.4 IRC
MEC18-01020 Final7/5/20187/5/20187/5/2018 9:16:44 AMAFAIL
Phone #: ###-#### Inspection requested via web by Sam Brown- primary and secondary drains needs ran out
MEC18-00233 Final7/5/20187/5/20187/5/2018 9:15:34 AMAFAIL
Phone #: ###-#### Inspection requested via web by Sam Brown- water heater flue needs 6" clearance to combustibles- need make up air for dry closet installed
MEC18-03167 Rough-in7/3/20187/5/20187/5/2018 9:14:38 AMAPASS
Phone #: ###-#### Inspection requested via web by Devony Bullard- R/I ok
MEC18-03167 Pressure Test7/3/20187/5/20187/5/2018 9:14:16 AMAPASS
Phone #: ###-#### Inspection requested via web by Devony Bullard- 20lb gas pass
MEC18-03161 Final7/3/20187/5/20187/5/2018 8:39:37 AMAFAIL
Inspection requested via web by Floyd Floyd Peek- need to support lineset on roof- need to seal lineset penetration on roof weather tight
MEC18-02979 Rough-in7/3/20187/5/20187/5/2018 8:36:38 AMAPASS
Carol Phone #: ###-####- outdoor fireplace R/I ok- call for final when completed
MEC17-02012 Mec-Aging Inspection7/5/20187/5/20187/5/2018 8:06:40 AM DONE
MEC17-02012 DOC - Permit Expired7/5/20187/5/20187/5/2018 8:06:30 AMAPASS
no call
MEC17-04650 Mec-Aging Inspection7/5/20187/5/20187/5/2018 8:05:58 AM DONE
MEC17-04650 Final7/5/20187/5/20187/5/2018 8:05:48 AMAPASS
MEC17-02039 DOC - Permit Expired7/5/20187/5/20187/5/2018 8:04:14 AMAPASS
no call