Inspections for the day of: Friday, July 5, 2019.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-02226 ELE-Aging Inspection7/5/20197/5/20197/8/2019 3:30:36 PM FAIL
Sent email to inform of aging permit. Waiting for response.
ELE19-00807 Final7/3/20197/5/20197/5/2019 10:44:02 AMAPASS
Phone #: ###-#### Inspection requested via web by William Andrews
Final ok
ELE19-01339 Final7/3/20197/5/20197/5/2019 10:43:38 AMAPASS
Phone #: ###-#### Inspection requested via web by William Andrews Final ok
ELE19-01425 Final7/3/20197/5/20197/5/2019 10:43:17 AMAFAIL
Phone #: ###-#### Inspection requested via web by William Andrews
210.8- All 15 or 20 map 120 volt receptacle outlets located with in 6' of a sink shall have GFCI protection. Washer
ELE19-01100 Final7/3/20197/5/20197/5/2019 9:47:40 AMAFAIL
garage code 2018 or 2019 Phone #: ###-#### Inspection requested via web by Darryn Coburn 200.9- White conductors used for other than grounded conductors shall be identified other than white at terminals. AC disconnect.
210.70- Each exterior door with grade level access shall have a luminaire installed controlled by a wall switch. Garage man door light no working.
House staged unable to test all receptacles.