Inspections for the day of: Wednesday, July 6, 2005.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-02379 Rough-In Permanent Service7/6/20057/6/20057/6/2005 4:16:11 PMPPASS
john ###-#### ric ok, p/s u/g n ok
ELE05-02377 Electrical Rough-In7/5/20057/6/20057/6/2005 4:15:24 PMPFAIL
Garage and service rough-in; Phone #: ###-#### Internet Inspection Request from: Tyler Bowen called contractor, told that concrete encased electrode required, bkrs need labels, ko's need closed. told we look at gec before pour and after pour
ELE05-02306 Rough-In Permanent Service7/6/20057/6/20057/6/2005 4:13:09 PMPFAIL
brandon; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa called left message, corr notice, 250.64(c) gec shall be installed in one continuous length without splice or joint, 300.4(D) nm cable shall be 1 1/4" from edge of framing member, 210.52(A)(2) wall space over 2' shall have recpt, BCC job id shall be posted, approved set of plans shall be on job
ELE05-02384 Electrical Rough-In7/6/20057/6/20057/6/2005 1:07:37 PMPPASS
Contact: Alex Kelly ; Phone #: ###-#### Internet Inspection Request from: Deb McCoy ok to cover walls and bath clg
ELE05-02380 Rough-In Permanent Service7/6/20057/6/20057/6/2005 12:29:22 PMPNR
clyde ###-#### nr, called left message.
ELE05-01902 Final7/6/20057/6/20057/6/2005 12:27:28 PMPPASS
Scheduled by a contractor via Hello! on 7/6/2005 at 8:33:26 AM. Contact: ###-####. called contr about loose wiring for dr recpt, ok to final
ELE05-02312 Temporary Service7/6/20057/6/20057/6/2005 12:22:42 PMPPASS
Scheduled by a contractor via Hello! on 7/6/2005 at 10:09:27 AM. Contact: ###-####. corr made, t/s u/g n ok
ELE05-02381 Rough-In Permanent Service7/6/20057/6/20057/6/2005 11:57:45 AMPPASS
clyde ###-#### ric ok, p/s u/g n ok
ELE05-01902 Final7/6/20057/6/20057/6/2005 10:38:47 AMACANC
Scheduled by a contractor via Hello! on 7/6/2005 at 6:38:03 AM. Contact: ###-####. see pm
ELE05-02270 Final7/5/20057/6/20057/6/2005 10:22:10 AMAFAIL
New service was install and is open for inspection; Phone #: ###-#### Internet Inspection Request from: Terry Ayers told owner he had to strap service cnd, use correct straps, use water tight listed emt connectors, ground elect cond to tie to gnded cnd in panel, put bushings on gnd wire, change dryer and range to 4 wire sys
ELE05-02220 Temporary Service7/5/20057/6/20057/6/2005 9:38:54 AMAPASS
vivian; Phone #: ###-#### Internet Inspection Request from: Barbara Moore t/s u/g n ok
ELE05-02219 Temporary Service7/5/20057/6/20057/6/2005 9:38:10 AMAPASS
vivian; Phone #: ###-#### Internet Inspection Request from: Barbara Moore t/s u/g n ok
ELE05-02194 Temporary Service7/5/20057/6/20057/6/2005 9:37:31 AMAPASS
vivian; Phone #: ###-#### Internet Inspection Request from: Barbara Moore t/s u/g n ok
ELE05-02221 Temporary Service7/5/20057/6/20057/6/2005 9:36:49 AMAPASS
vivian; Phone #: ###-#### Internet Inspection Request from: Barbara Moore t/s u/g n ok
ELE05-02375 Permanent Service7/5/20057/6/20057/6/2005 9:35:19 AMAPASS
mike-- ###-#### called contr p/s o/h exst ok
ELE05-02218 Temporary Service7/5/20057/6/20057/6/2005 9:26:26 AMAFAIL
vivian; Phone #: ###-#### Internet Inspection Request from: Barbara Moore 408.7 blank shall be closed,called contr, fee due
ELE05-01872 Final7/6/20057/6/20057/6/2005 8:33:31 AMANR
Scheduled by a contractor via Hello! on 7/6/2005 at 6:41:24 AM. too many items not done. callrd contr, he will call when done.
ELE04-03723 Electrical Rough-In7/6/20057/6/20057/6/2005 8:16:08 AMAPASS
Scheduled by a contractor via Hello! on 7/6/2005 at 7:17:02 AM. 1st floor central area ok to cover clg