ELE05-02379
| Rough-In Permanent Service | 7/6/2005 | 7/6/2005 | 7/6/2005 4:16:11 PM | P | PASS |
|
|
john ###-#### ric ok, p/s u/g n ok
|
ELE05-02377
| Electrical Rough-In | 7/5/2005 | 7/6/2005 | 7/6/2005 4:15:24 PM | P | FAIL |
|
|
Garage and service rough-in; Phone #: ###-#### Internet Inspection Request from: Tyler Bowen called contractor, told that concrete encased electrode required, bkrs need labels, ko's need closed. told we look at gec before pour and after pour
|
ELE05-02306
| Rough-In Permanent Service | 7/6/2005 | 7/6/2005 | 7/6/2005 4:13:09 PM | P | FAIL |
|
|
brandon; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa called left message, corr notice, 250.64(c) gec shall be installed in one continuous length without splice or joint, 300.4(D) nm cable shall be 1 1/4" from edge of framing member, 210.52(A)(2) wall space over 2' shall have recpt, BCC job id shall be posted, approved set of plans shall be on job
|
ELE05-02384
| Electrical Rough-In | 7/6/2005 | 7/6/2005 | 7/6/2005 1:07:37 PM | P | PASS |
|
|
Contact: Alex Kelly ; Phone #: ###-#### Internet Inspection Request from: Deb McCoy ok to cover walls and bath clg
|
ELE05-02380
| Rough-In Permanent Service | 7/6/2005 | 7/6/2005 | 7/6/2005 12:29:22 PM | P | NR |
|
|
clyde ###-#### nr, called left message.
|
ELE05-01902
| Final | 7/6/2005 | 7/6/2005 | 7/6/2005 12:27:28 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 7/6/2005 at 8:33:26 AM. Contact: ###-####. called contr about loose wiring for dr recpt, ok to final
|
ELE05-02312
| Temporary Service | 7/6/2005 | 7/6/2005 | 7/6/2005 12:22:42 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 7/6/2005 at 10:09:27 AM. Contact: ###-####. corr made, t/s u/g n ok
|
ELE05-02381
| Rough-In Permanent Service | 7/6/2005 | 7/6/2005 | 7/6/2005 11:57:45 AM | P | PASS |
|
|
clyde ###-#### ric ok, p/s u/g n ok
|
ELE05-01902
| Final | 7/6/2005 | 7/6/2005 | 7/6/2005 10:38:47 AM | A | CANC |
|
|
Scheduled by a contractor via Hello! on 7/6/2005 at 6:38:03 AM. Contact: ###-####. see pm
|
ELE05-02270
| Final | 7/5/2005 | 7/6/2005 | 7/6/2005 10:22:10 AM | A | FAIL |
|
|
New service was install and is open for inspection; Phone #: ###-#### Internet Inspection Request from: Terry Ayers told owner he had to strap service cnd, use correct straps, use water tight listed emt connectors, ground elect cond to tie to gnded cnd in panel, put bushings on gnd wire, change dryer and range to 4 wire sys
|
ELE05-02220
| Temporary Service | 7/5/2005 | 7/6/2005 | 7/6/2005 9:38:54 AM | A | PASS |
|
|
vivian; Phone #: ###-#### Internet Inspection Request from: Barbara Moore t/s u/g n ok
|
ELE05-02219
| Temporary Service | 7/5/2005 | 7/6/2005 | 7/6/2005 9:38:10 AM | A | PASS |
|
|
vivian; Phone #: ###-#### Internet Inspection Request from: Barbara Moore t/s u/g n ok
|
ELE05-02194
| Temporary Service | 7/5/2005 | 7/6/2005 | 7/6/2005 9:37:31 AM | A | PASS |
|
|
vivian; Phone #: ###-#### Internet Inspection Request from: Barbara Moore t/s u/g n ok
|
ELE05-02221
| Temporary Service | 7/5/2005 | 7/6/2005 | 7/6/2005 9:36:49 AM | A | PASS |
|
|
vivian; Phone #: ###-#### Internet Inspection Request from: Barbara Moore t/s u/g n ok
|
ELE05-02375
| Permanent Service | 7/5/2005 | 7/6/2005 | 7/6/2005 9:35:19 AM | A | PASS |
|
|
mike-- ###-#### called contr p/s o/h exst ok
|
ELE05-02218
| Temporary Service | 7/5/2005 | 7/6/2005 | 7/6/2005 9:26:26 AM | A | FAIL |
|
|
vivian; Phone #: ###-#### Internet Inspection Request from: Barbara Moore 408.7 blank shall be closed,called contr, fee due
|
ELE05-01872
| Final | 7/6/2005 | 7/6/2005 | 7/6/2005 8:33:31 AM | A | NR |
|
|
Scheduled by a contractor via Hello! on 7/6/2005 at 6:41:24 AM. too many items not done. callrd contr, he will call when done.
|
ELE04-03723
| Electrical Rough-In | 7/6/2005 | 7/6/2005 | 7/6/2005 8:16:08 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 7/6/2005 at 7:17:02 AM. 1st floor central area ok to cover clg
|