BLD05-00876
| FIRE-Final Inspection | 7/6/2005 | 7/6/2005 | 7/6/2005 4:07:41 PM | P | FAIL |
|
|
Provide testing and verification of emergency lights installed as shown in locations on approved plans.
|
BLD05-00876
| FIRE-Alarm Testing | 7/6/2005 | 7/6/2005 | 7/6/2005 4:04:58 PM | P | CANC |
|
|
Duplicate inspection for life safety.
|
BLD05-00876
| FIRE-Conference | 7/6/2005 | 7/6/2005 | 7/6/2005 2:16:30 PM | P | DONE |
|
|
Discussed req. for fire sprinkler final.
|
FIR04-00749
| INSP-Sprinkler Rough-in/Hydro | 7/5/2005 | 7/6/2005 | 7/6/2005 12:07:20 PM | A | PART |
|
|
Remote FDC piping hydrostatic test passed.
|
BLD04-02505
| FIRE-Final Inspection | 7/5/2005 | 7/6/2005 | 7/6/2005 11:35:22 AM | A | PASS |
|
|
Fire life safety finaled.
|
FIR05-00306
| INSP-Sprinkler Rough-in/Hydro | 7/5/2005 | 7/6/2005 | 7/6/2005 10:55:08 AM | A | FAIL |
|
|
Provide proper temp. head at location directly in front at soffit above recessed fireplace to meet req. of NFPA table 6.2.5.1.
|
FIR05-00111
| INSP-Sprinkler Rough-in/Hydro | 7/5/2005 | 7/6/2005 | 7/6/2005 10:49:41 AM | A | FAIL |
|
|
Need lateral EQ brace installed on the last piece of main 2nd floor SW side per NFPA 13 9.3.5.3.4, attatch retaining straps in two locations 2nd floor, missing hangers on penthouse branch line supply, provide guages at floor control manifolds as shown on approved plans.
|
FIR05-00313
| INSP-Final Inspection | 7/6/2005 | 7/6/2005 | 7/6/2005 12:00:00 AM | A | PASS |
|
|
Inspection satisfactory, permit finaled.
|
FIR05-00383
| INSP-Final Inspection | 7/6/2005 | 7/6/2005 | 7/6/2005 12:00:00 AM | A | PASS |
|
|
HVAC units shut down upon smoke detection, fire alarm finaled.
|
FIR05-00062
| INSP-Final Inspection | 7/6/2005 | 7/6/2005 | 7/6/2005 12:00:00 AM | A | PASS |
|
|
Fire sprinkler finaled.
|
FIR05-00111
| INSP-Final Inspection | 7/6/2005 | 7/6/2005 | 7/6/2005 12:00:00 AM | P | PART |
|
|
Overhead hydrostatic test of 2nd and 3rd floor shell pipe passed.
|
FIR05-00208
| INSP-Final Inspection | 7/6/2005 | 7/6/2005 | 7/6/2005 12:00:00 AM | P | PASS |
|
|
Fire sprinkler finaled.
|