Inspections for the day of: Wednesday, July 6, 2005.
Number of inspections: 3
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00216 INSP-Final Inspection6/29/20057/6/20057/6/2005 4:48:45 PMPPASS
Permit finaled
BLD05-00353 FIRE-Final Inspection7/5/20057/6/20057/6/2005 12:23:40 PMAFAIL
Repair all three exit signs, provide two emergency lights,one at the front and one at the back. Provide nonlocking hardware on the back door to short corridor. Provide one 2A10BC fire extinguisher with current inspection tag and mounted at 48" AFF. Remove thumbturn from main exit, keyed hardware is ok. Provide automatic flush bolts for the main exit. Provide "Door to remain unlocked when building is occupied" sticker at the main exit. Remove manual flush bolts from the rear door active leaf.
BLD04-00845 FIRE-Final Inspection7/6/20057/6/20057/6/2005 12:00:00 AMPPASS
fire life safety finaled