FIR05-00216
| INSP-Final Inspection | 6/29/2005 | 7/6/2005 | 7/6/2005 4:48:45 PM | P | PASS |
|
|
Permit finaled
|
BLD05-00353
| FIRE-Final Inspection | 7/5/2005 | 7/6/2005 | 7/6/2005 12:23:40 PM | A | FAIL |
|
|
Repair all three exit signs, provide two emergency lights,one at the front and one at the back. Provide nonlocking hardware on the back door to short corridor. Provide one 2A10BC fire extinguisher with current inspection tag and mounted at 48" AFF. Remove thumbturn from main exit, keyed hardware is ok. Provide automatic flush bolts for the main exit. Provide "Door to remain unlocked when building is occupied" sticker at the main exit. Remove manual flush bolts from the rear door active leaf.
|
BLD04-00845
| FIRE-Final Inspection | 7/6/2005 | 7/6/2005 | 7/6/2005 12:00:00 AM | P | PASS |
|
|
fire life safety finaled
|