Inspections for the day of: Thursday, July 6, 2006.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-02116 Electrical Rough-In7/6/20067/6/20067/6/2006 3:42:29 PMPPASS
need rough in on new building.thank you.; Phone #: ###-#### x Internet Inspection Request from: BRIAN KEITH walls and ceilings ok
ELE06-01200 Final7/6/20067/6/20067/6/2006 3:02:11 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Zane Robertson ok
ELE06-01199 Final7/6/20067/6/20067/6/2006 3:01:50 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Zane Robertson ok
ELE06-01198 Final7/6/20067/6/20067/6/2006 3:01:34 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Zane Robertson ok
ELE06-01197 Final7/6/20067/6/20067/6/2006 3:01:13 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Zane Robertson ok
ELE06-01810 Permanent Service7/5/20067/6/20067/6/2006 2:26:26 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Tim Lawrence p/s u/g new ok
ELE06-01755 Rough-In Permanent Service6/29/20067/6/20067/6/2006 2:07:57 PMPPASS
DAVE; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
p/s u/g rec. ok for both meters
ELE06-02371 Electrical Rough-In7/6/20067/6/20067/6/2006 1:07:26 PMPFAIL
tim- call prior for access - ###-#### Internet Inspection Request from: Barbara Buckley corr. met owner, not all violations made and new ones created, 314.16 box fill, 314.43 nails inside plastic boxes outside recepts, 314.20 boxes still not flush with siding, 300.14 free length of conductor owner cut wires short after Bob's inspection, 110.14 needs devices for all splices just twisted wires note told owner to check all locations for box fill not just one box I found
ELE06-02116 Permanent Service7/6/20067/6/20067/6/2006 11:53:54 AMPPASS
need rough in on new building.thank you.; Phone #: ###-#### x Internet Inspection Request from: BRIAN KEITH
p/s u/g new ok
ELE06-02489 Rough-In Permanent Service7/5/20067/6/20067/6/2006 11:13:12 AMAPASS
rick; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley
r/i p/s u/g new ok
ELE06-00182 Electrical Rough-In7/5/20067/6/20067/6/2006 10:50:34 AMAPASS
Approval to cover trench; Phone #: ###-#### Internet Inspection Request from: Alan Lusk ok
ELE06-00409 Final7/5/20067/6/20067/6/2006 10:24:59 AMAPART
damon; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles t/o ok phone contractor needs high voltage rated wire in cabinet 300.3(C)(1)
ELE06-02364 Electrical Rough-In7/5/20067/6/20067/6/2006 10:22:28 AMAPART
Scheduled by a contractor via Hello! on 7/5/2006 at 3:46:44 PM. Contact: ###-####. pool & spa bond only no equip. grid
ELE06-02493 Electrical Rough-In7/5/20067/6/20067/6/2006 9:38:00 AMAFAIL
wall r/i --shawn ###-#### cell corr. called left message300.4 nail plates & 11/4", 314.16 box fill new plastic cutin and old steel boxes, 314.25(D) needs listed fan boxes, 314.20 boxes shall be flush with combustible material, set back no more than 1/4 in other, 210.52(A) outlet spacing din rm & room north of din. rm 250.148 grd metal boxes, note cable sheath shall extend into box S W bed rm cable for outside recept, check for correct small appliance branch circuits
ELE06-01268 Final7/5/20067/6/20067/6/2006 9:02:34 AMAPART
blake or damon at ###-####- call for access prior to insp ; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley
t/o ok only needs 300 volt rated phone cable in elevator control cabinet 300.3(C)(1) card signed