ELE11-01393
| Rough-In Permanent Service | 7/6/2011 | 7/6/2011 | 7/6/2011 4:54:00 PM | P | NR |
|
|
Phone #: ###-#### >> Inspection requested via web by Tracy Robertson called, left message, shall post available fault current at panel, shall protect cables within 6' of attic access, left correction notice
|
ELE11-01460
| Rough-In Permanent Service | 7/6/2011 | 7/6/2011 | 7/6/2011 4:52:11 PM | P | NR |
|
|
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson called, said to recall, also wrong address, no grounding done, one panel not up, no weather-head on the panel that was up
|
ELE11-00845
| Conference | 7/6/2011 | 7/6/2011 | 7/6/2011 3:02:20 PM | P | DONE |
|
|
pete Phone #: ###-#### talked about wiring outbuilding
|
ELE11-00929
| Final | 7/6/2011 | 7/6/2011 | 7/6/2011 2:44:16 PM | P | PASS |
|
|
Mel Phone #: ###-#### ok final
|
ELE10-02676
| Electrical Rough-In | 7/6/2011 | 7/6/2011 | 7/6/2011 1:09:44 PM | P | PART |
|
|
Second floor grid inspection. Contact on job is Tom Hackman. Phone #: ###-#### >> Inspection requested via web by Richard Montgomery second floor ceiling except 2 rooms up ramp ok- not supposed to be any borders up
|
ELE11-01431
| Final | 7/1/2011 | 7/6/2011 | 7/6/2011 10:36:25 AM | A | PASS |
|
|
Heedo Phone #: ###-#### ok final
|
ELE11-01381
| Electrical Rough-In | 7/5/2011 | 7/6/2011 | 7/6/2011 10:17:45 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by BARRY KENDALL re-located panel ok cover wall
|
ELE11-01401
| Final | 7/5/2011 | 7/6/2011 | 7/6/2011 9:51:36 AM | A | PASS |
|
|
IPCO LIGHTING EASY UP-GRADE Inspection. Contact Chad Van Orden at: ###-####. He is the journeyman on site.
Thanks Jack! Phone #: ###-#### >> Inspection requested via web by Todd Sellman ok final
|
ELE11-01444
| Rough-In Permanent Service | 7/5/2011 | 7/6/2011 | 7/6/2011 9:31:47 AM | A | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by Dan Rohl called, left message, left correction notice, NEC 300.4(A)(1) edge of bored holes shall be 1 1/4" from edge of framing members, 334.30 shall strap nm cable within 12" of box, shall not staple flat cable on edge, 210.52(A)(1) receptacles shall be spaced such that no point along wall is over 6' from an outlet, 110.12(A) cable shall not be damaged, BCC shall terminate all conductors in boxes
|
ELE11-01436
| Temporary Service | 7/5/2011 | 7/6/2011 | 7/6/2011 8:42:50 AM | A | FAIL |
|
|
Jason Phone #: ###-#### called, left correction notice, NEC 312.5 all conductors shall have abrasion protection, 406.8(B) shall use listed weather-proof receptacles, 110.12(B) there shall be no broken parts, 408.4 shall provide circuit directory
|
ELE11-01443
| Electrical Rough-In | 7/5/2011 | 7/6/2011 | 7/6/2011 8:37:00 AM | A | PASS |
|
|
george Phone #: ###-#### called, left message, walls only ok cover
|
ELE10-02830
| ELE-Aging Inspection | 7/6/2011 | 7/6/2011 | 7/6/2011 7:25:02 AM | | DONE |
|
|
still under construction
|
ELE10-01875
| ELE-Aging Inspection | 7/6/2011 | 7/6/2011 | 7/6/2011 7:24:27 AM | | DONE |
|
|
still under construction
|