Inspections for the day of: Wednesday, July 6, 2011.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE11-01393 Rough-In Permanent Service7/6/20117/6/20117/6/2011 4:54:00 PMPNR
Phone #: ###-#### >> Inspection requested via web by Tracy Robertson called, left message, shall post available fault current at panel, shall protect cables within 6' of attic access, left correction notice
ELE11-01460 Rough-In Permanent Service7/6/20117/6/20117/6/2011 4:52:11 PMPNR
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson called, said to recall, also wrong address, no grounding done, one panel not up, no weather-head on the panel that was up
ELE11-00845 Conference7/6/20117/6/20117/6/2011 3:02:20 PMPDONE
pete Phone #: ###-#### talked about wiring outbuilding
ELE11-00929 Final7/6/20117/6/20117/6/2011 2:44:16 PMPPASS
Mel Phone #: ###-#### ok final
ELE10-02676 Electrical Rough-In7/6/20117/6/20117/6/2011 1:09:44 PMPPART
Second floor grid inspection. Contact on job is Tom Hackman. Phone #: ###-#### >> Inspection requested via web by Richard Montgomery second floor ceiling except 2 rooms up ramp ok- not supposed to be any borders up
ELE11-01431 Final7/1/20117/6/20117/6/2011 10:36:25 AMAPASS
Heedo Phone #: ###-#### ok final
ELE11-01381 Electrical Rough-In7/5/20117/6/20117/6/2011 10:17:45 AMAPASS
Phone #: ###-#### >> Inspection requested via web by BARRY KENDALL re-located panel ok cover wall
ELE11-01401 Final7/5/20117/6/20117/6/2011 9:51:36 AMAPASS
IPCO LIGHTING EASY UP-GRADE Inspection. Contact Chad Van Orden at: ###-####. He is the journeyman on site.

Thanks Jack! Phone #: ###-#### >> Inspection requested via web by Todd Sellman ok final
ELE11-01444 Rough-In Permanent Service7/5/20117/6/20117/6/2011 9:31:47 AMAFAIL
Phone #: ###-#### >> Inspection requested via web by Dan Rohl called, left message, left correction notice, NEC 300.4(A)(1) edge of bored holes shall be 1 1/4" from edge of framing members, 334.30 shall strap nm cable within 12" of box, shall not staple flat cable on edge, 210.52(A)(1) receptacles shall be spaced such that no point along wall is over 6' from an outlet, 110.12(A) cable shall not be damaged, BCC shall terminate all conductors in boxes
ELE11-01436 Temporary Service7/5/20117/6/20117/6/2011 8:42:50 AMAFAIL
Jason Phone #: ###-#### called, left correction notice, NEC 312.5 all conductors shall have abrasion protection, 406.8(B) shall use listed weather-proof receptacles, 110.12(B) there shall be no broken parts, 408.4 shall provide circuit directory
ELE11-01443 Electrical Rough-In7/5/20117/6/20117/6/2011 8:37:00 AMAPASS
george Phone #: ###-#### called, left message, walls only ok cover
ELE10-02830 ELE-Aging Inspection7/6/20117/6/20117/6/2011 7:25:02 AM DONE
still under construction
ELE10-01875 ELE-Aging Inspection7/6/20117/6/20117/6/2011 7:24:27 AM DONE
still under construction