Inspections for the day of: Friday, July 6, 2012.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR12-00206 INSP-Final Inspection7/6/20127/6/20127/6/2012 5:11:32 PMPPASS
Previous correction items verified for completion. Fire sprinkler permit final approved.
BLD10-02771 FIRE-Final Inspection7/6/20127/6/20127/6/2012 3:17:43 PMPPASS
Final fire life safety inspection completed satisfactory. Contractor to repair one EM discharge light above the main entry/exit as discussed.
FIR12-00314 INSP-Sprinkler Rough-in7/6/20127/6/20127/6/2012 1:51:01 PMAPART
Overhead fire sprinkler rough-in at the additional office area okayed.
BLD10-02771 FIRE-Conference7/6/20127/6/20127/6/2012 1:47:58 PMADONE
Regarding life safety conditions for final occupancy approval.
FIR11-00496 INSP-Conference7/6/20127/6/20127/6/2012 1:47:06 PMADONE
Regarding off site monitoring.
BLD12-00441 FIRE-Final Inspection7/3/20127/6/20127/6/2012 1:46:04 PMAFAIL
Door hardware at the main entry/exit and the second exit needs revised, one exit sign is not functional on battery backup, both exit discharge lights need repaired.