Inspections for the day of: Monday, July 6, 2015.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-01515 Final7/6/20157/6/20157/6/2015 4:50:48 PMPPASS
Phone #: ###-#### Inspection requested via web by TOM BICANDI Final ok
ELE15-02026 Electrical Rough-In7/2/20157/6/20157/6/2015 4:03:33 PMPPASS
Wall Inspection, Geoff Hannaford is contact on this project. ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce Wall rough in ok cover
ELE15-02042 Electrical Rough-In7/5/20157/6/20157/6/2015 3:55:17 PMPFAIL
Please call 30 minutes advance notice ###-#### Thanks, Mike Inspection requested via web by Mike Swift Horzontal NM cable shall be protected from physical damage below 8'.
230.79- Minimum feeders- more than 2 circuits shall be 60 amp minimum or reduce number of circuits to 2 and 30 disconnect.
210.8- Outdoor work shed all 120 volt 15 or 20 amp receptacle outlets shall have GFCI protection
Verbal correction with contractor on site
ELE15-01824 Electrical Rough-In7/1/20157/6/20157/6/2015 2:44:47 PMPPASS
We are requesting a wall rough in inspection for Monday 7/6/15 in the PM. Our onsite contact is Rich @ ###-####. Thank you, Phone #: ###-#### Inspection requested via web by Clint Tate Dividing old lobby area into 3 different rooms. Wall rough in ok cover
ELE15-00619 Final7/2/20157/6/20157/6/2015 2:13:49 PMAPASS
Phone #: ###-#### Inspection requested via web by Lee VanSchoiack Final ok
ELE15-01978 Electrical Rough-In7/6/20157/6/20157/6/2015 1:25:23 PMPPASS
Phone #: ###-#### Inspection requested via web by Kevin Burke Upstairs walls and ceilings stripped due to fire damage. Rough in ok cover
ELE15-01968 Final7/2/20157/6/20157/6/2015 1:07:18 PMAPASS
Phone #: ###-#### Inspection requested via web by kendall bender Final ok
ELE15-02037 Rough-In Permanent Service7/3/20157/6/20157/6/2015 12:51:03 PMAFAIL
Dan Phone #: ###-#### Inspection requested via web by Dan Hobdey 110.11- Concrete encased rebar exposed to weather outdoors will rust. Ground rods shall be added or rebar shall be located in wall.
300.4- NM cable where enters fireplace shall have bushing.
300.4- NM cable shall be protected from physical damage where ran through bored holes that do not maintain 1 1/4" from framing surface. 45 degree corners.
ELE15-02028 Electrical Rough-In7/2/20157/6/20157/6/2015 10:41:47 AMAPART
Underground; Jim Phone #: ###-#### East half for gear. Underground for charging stations in future. rough in for gear ok cover
ELE15-01413 Electrical Rough-In7/2/20157/6/20157/6/2015 10:14:15 AMAPART
We are requesting a partial ceiling inspection for Monday July 6th in the AM. Our onsite contact is Bud @ ###-####. Thank you! Phone #: ###-#### Inspection requested via web by Clint Tate North half as noted on contractor print, to leave tile out for exit signs not in yet. Grid rough in as noted ok cover
ELE15-01700 Electrical Rough-In7/2/20157/6/20157/6/2015 9:35:36 AMAPASS
Max Phone #: ###-#### Walls and hardlids rough in ok cover
ELE15-01698 Electrical Rough-In7/2/20157/6/20157/6/2015 9:21:20 AMAFAIL
This is a floor heat circuit inspection only. Homeowners will be on site. Thanks. Phone #: ###-#### Inspection requested via web by Paula Gratiot 110.3- As per manufacturers instructions cold lead splice, heat cable end and sensor shall be recessed in sub floor.
ELE15-02043 Rough-In Permanent Service7/6/20157/6/20157/6/2015 8:58:05 AMAPASS
Phone #: ###-#### Inspection requested via web by TOM BICANDI Rough in ok cover p/s u/g n ok