ELE15-01515
| Final | 7/6/2015 | 7/6/2015 | 7/6/2015 4:50:48 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI Final ok
|
ELE15-02026
| Electrical Rough-In | 7/2/2015 | 7/6/2015 | 7/6/2015 4:03:33 PM | P | PASS |
|
|
Wall Inspection, Geoff Hannaford is contact on this project. ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce Wall rough in ok cover
|
ELE15-02042
| Electrical Rough-In | 7/5/2015 | 7/6/2015 | 7/6/2015 3:55:17 PM | P | FAIL |
|
|
Please call 30 minutes advance notice ###-#### Thanks, Mike Inspection requested via web by Mike Swift Horzontal NM cable shall be protected from physical damage below 8'. 230.79- Minimum feeders- more than 2 circuits shall be 60 amp minimum or reduce number of circuits to 2 and 30 disconnect. 210.8- Outdoor work shed all 120 volt 15 or 20 amp receptacle outlets shall have GFCI protection Verbal correction with contractor on site
|
ELE15-01824
| Electrical Rough-In | 7/1/2015 | 7/6/2015 | 7/6/2015 2:44:47 PM | P | PASS |
|
|
We are requesting a wall rough in inspection for Monday 7/6/15 in the PM. Our onsite contact is Rich @ ###-####. Thank you, Phone #: ###-#### Inspection requested via web by Clint Tate Dividing old lobby area into 3 different rooms. Wall rough in ok cover
|
ELE15-00619
| Final | 7/2/2015 | 7/6/2015 | 7/6/2015 2:13:49 PM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Lee VanSchoiack Final ok
|
ELE15-01978
| Electrical Rough-In | 7/6/2015 | 7/6/2015 | 7/6/2015 1:25:23 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kevin Burke Upstairs walls and ceilings stripped due to fire damage. Rough in ok cover
|
ELE15-01968
| Final | 7/2/2015 | 7/6/2015 | 7/6/2015 1:07:18 PM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by kendall bender Final ok
|
ELE15-02037
| Rough-In Permanent Service | 7/3/2015 | 7/6/2015 | 7/6/2015 12:51:03 PM | A | FAIL |
|
|
Dan Phone #: ###-#### Inspection requested via web by Dan Hobdey 110.11- Concrete encased rebar exposed to weather outdoors will rust. Ground rods shall be added or rebar shall be located in wall. 300.4- NM cable where enters fireplace shall have bushing. 300.4- NM cable shall be protected from physical damage where ran through bored holes that do not maintain 1 1/4" from framing surface. 45 degree corners.
|
ELE15-02028
| Electrical Rough-In | 7/2/2015 | 7/6/2015 | 7/6/2015 10:41:47 AM | A | PART |
|
|
Underground; Jim Phone #: ###-#### East half for gear. Underground for charging stations in future. rough in for gear ok cover
|
ELE15-01413
| Electrical Rough-In | 7/2/2015 | 7/6/2015 | 7/6/2015 10:14:15 AM | A | PART |
|
|
We are requesting a partial ceiling inspection for Monday July 6th in the AM. Our onsite contact is Bud @ ###-####. Thank you! Phone #: ###-#### Inspection requested via web by Clint Tate North half as noted on contractor print, to leave tile out for exit signs not in yet. Grid rough in as noted ok cover
|
ELE15-01700
| Electrical Rough-In | 7/2/2015 | 7/6/2015 | 7/6/2015 9:35:36 AM | A | PASS |
|
|
Max Phone #: ###-#### Walls and hardlids rough in ok cover
|
ELE15-01698
| Electrical Rough-In | 7/2/2015 | 7/6/2015 | 7/6/2015 9:21:20 AM | A | FAIL |
|
|
This is a floor heat circuit inspection only. Homeowners will be on site. Thanks. Phone #: ###-#### Inspection requested via web by Paula Gratiot 110.3- As per manufacturers instructions cold lead splice, heat cable end and sensor shall be recessed in sub floor.
|
ELE15-02043
| Rough-In Permanent Service | 7/6/2015 | 7/6/2015 | 7/6/2015 8:58:05 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI Rough in ok cover p/s u/g n ok
|