Inspections for the day of: Monday, July 6, 2015.
Number of inspections: 22
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Little
TitlePLM-INSPECTOR
Phone #869-5166
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
PLM15-01271 Final7/6/20157/6/20157/6/2015 4:38:54 PMPPASS
JOB # 13065. Phone #: ###-#### Inspection requested via web by Ann Marie Reyes
PLM15-00606 Plumbing Rough-in7/6/20157/6/20157/6/2015 4:16:28 PMPPASS
Please come after 4:00 Thanks Phone #: ###-#### Inspection requested via web by Erin Whiting
PLM15-02229 Sprinkler (Final)7/6/20157/6/20157/6/2015 4:15:53 PMPPASS
Phone #: ###-#### Inspection requested via web by mitchell jedrick
PLM15-00384 Water Heater Final7/6/20157/6/20157/6/2015 3:30:23 PMPPASS
carbon monoxide detecs installed.
PLM15-00374 DOC - Permit Finaled7/6/20157/6/20157/6/2015 3:06:11 PMPPASS
PLM15-00323 DOC - Permit Finaled7/6/20157/6/20157/6/2015 2:49:28 PMPPASS
PLM14-02990 DOC - Permit Finaled7/6/20157/6/20157/6/2015 2:41:18 PMPPASS
PLM14-02990 PLM-Aging Inspection7/6/20157/6/20157/6/2015 2:41:06 PM PASS
backflow certified on 4/8/15.
PLM15-01877 Final7/6/20157/6/20157/6/2015 2:22:31 PMPPASS
Luke Phone #: ###-####
MIS15-00159 PLM-Conference7/2/20157/6/20157/6/2015 2:00:33 PMPPART
Mariela Phone #: ###-####======need all backflow devices certified including lawn sprinkler, have plumber add device's for ice maker and coffee if needed.
PLM15-02181 Final7/6/20157/6/20157/6/2015 1:14:46 PMPFAIL
Backflow // Tom Phone #: 1-###-####=======remove all black iron material and replace with approved material, install a union within 12" of device. DO NOT BURY
PLM15-02208 DOC - Permit Finaled7/6/20157/6/20157/6/2015 12:56:57 PMPPASS
PLM15-02208 Water and/or Sewer7/6/20157/6/20157/6/2015 12:56:36 PMPPASS
Phone #: ###-#### Inspection requested via web by Vicki Tallent
PLM15-02227 Water and/or Sewer7/6/20157/6/20157/6/2015 11:44:49 AMAFAIL
Phone #: ###-#### Inspection requested via web by Brett Simmons=======cannot see water line, tracer wire not with water line, sewer only ok to bury
PLM15-00601 Final7/3/20157/6/20157/6/2015 11:31:30 AMAPASS
Phone #: ###-#### Inspection requested via web by Erin Whiting
PLM15-01583 Plumbing Rough-in7/2/20157/6/20157/6/2015 10:50:56 AMAPART
if questions call Joe @ ###-#### Phone #: ###-#### Inspection requested via web by Stacia Haumann==========sink RI for bi-plane remodel ok
PLM15-01696 Groundwork7/2/20157/6/20157/6/2015 10:18:47 AMAPART
RYAN IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER=========GW partial ok
PLM15-01725 Final7/3/20157/6/20157/6/2015 10:01:59 AMAFAIL
Job is ready for final. Contractor will be on site. Phone #: ###-#### Inspection requested via web by Scott Sparrell=====Pipe t&p outside, temper all faucets per 413.1,need open front water closet seats, Shower not done, backflow protection, correction notice left on WH
PLM15-01441 Final7/3/20157/6/20157/6/2015 9:22:30 AMAFAIL
Garage code 5151 Phone #: ###-#### Inspection requested via web by Robert Madrigal==========1. T&P needs an approved airgap or piped to garage floor,. 2. remove plug from hub drain and washer box.
PLM15-00817 Final7/3/20157/6/20157/6/2015 8:56:40 AMAFAIL
Please call Brett @ ###-#### for access. Phone #: ###-#### Inspection requested via web by Brett Lee======lav faucet does not comply with 413.1 of the UPC, need to install an under lav tempering device that meets ASSE 1070 standards.
PLM15-02208 Water and/or Sewer7/2/20157/6/20157/6/2015 8:32:41 AMAFAIL
Phone #: ###-#### Inspection requested via web by Vicki Tallent====address posted does not match site map, if it is the correct job it is not ready. please have address corrected before reinspection
PLM15-01877 Water and/or Sewer7/2/20157/6/20157/6/2015 12:00:00 AMACANC
Final Inspection - Contact is Luke Karel ###-#### Phone #: ###-#### >> Inspection requested via web by Rusty Karel