Inspections for the day of: Monday, July 6, 2015.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDaryl DeGrange
TitleELE-INSPECTION SUPV
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
GRD15-00018 GRD-Other7/6/20157/6/20157/7/2015 8:24:52 AMPCANC
Request ins. For temporary power pole at job job trailer. Phone #: ###-#### >> Inspection requested via web by Barry Willoughby Inspection cancelled from web by: Barry Willoughby
ELE14-03518 Electrical Rough-In7/6/20157/6/20157/6/2015 4:48:32 PMPFAIL
would like call ahead; J.D. Phone #: ###-#### NEC 300.4 shall not staple NM cable within 1 1/4 of edge of framing member, NEC 334.30 Secure MN cable within 12in. of cabnet, device box. Grounded conductor in neutral bar and grounding conductors in ground bar, Decaded bathroom circuit not serve other receptacles of other rooms
ELE15-01736 Final7/3/20157/6/20157/6/2015 4:05:00 PMPFAIL
The house is behind another house. First right east of Haines.
Call jerry with any questions Phone #: ###-#### Inspection requested via web by Dave Brueggemann Complete grounded conductor to house metermain, install all strands of grounding conductor in ground bar, replace 100 amp overcurrent device with 60 ampere
ELE15-02022 Permanent Service7/2/20157/6/20157/6/2015 2:47:51 PMPPASS
Phone #: ###-#### Inspection requested via web by Lee VanSchoiack p/s u/g n ok
ELE14-02371 Electrical Rough-In7/1/20157/6/20157/6/2015 2:19:21 PMPPASS
Rough in hard lid inspection IL building area F 4th floor rooms F451, F452, F453, F454, F456. Building permit number BLD13-00187. Call Fabian when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum rough-in ok cover hard lid as noted
ELE14-02066 Permanent Service7/1/20157/6/20157/6/2015 2:16:17 PMPFAIL
Permanent service inspection for SNF K. Building permit number BLD13-00190. Call Fabian when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum NEC 240.24(A) Highest position a breaker can be installed is 6ft 7in.
ELE15-00861 Final7/3/20157/6/20157/6/2015 1:18:07 PMPCANC
blanket permit for bldg. 80. Phone #: ###-#### Inspection requested via web by Steve Moss contractor wants to reschedule for next week
ELE15-00860 Final7/3/20157/6/20157/6/2015 1:16:35 PMPCANC
blanket permit for site electrical work. Phone #: ###-#### Inspection requested via web by Steve Moss contractor wants to reschedule for next week
ELE15-00859 Final7/3/20157/6/20157/6/2015 1:14:58 PMPCANC
blanket permit for bldg. 1x work Phone #: ###-#### Inspection requested via web by Steve Moss contractor wants to reschedule for next week
ELE15-01505 Final7/5/20157/6/20157/6/2015 1:12:06 PMAPASS
Please call 30 mins ahead Phone #: ###-#### Inspection requested via web by John VanZandt final ok
ELE15-00895 Final7/3/20157/6/20157/6/2015 1:11:57 PMACANC
Phone #: ###-#### Inspection requested via web by Eric Landberg contractor wants to reschedule for next week
ELE15-00894 Final7/3/20157/6/20157/6/2015 1:11:18 PMACANC
Phone #: ###-#### Inspection requested via web by Eric Landberg contractor wants to reschedule for next week
ELE15-00863 Final7/3/20157/6/20157/6/2015 11:49:19 AMACANC
Final on blanket for ken heller Phone #: ###-#### Inspection requested via web by Ken Heller contractor wants to reschedule for next week
ELE15-01577 Final7/2/20157/6/20157/6/2015 10:06:36 AMAPART
Check in with Security for visitors badge. Call Steve when in route. Phone #: ###-#### Inspection requested via web by Steve McCloy Partial final for phase one Temporary occupancy ok
ELE15-01577 Electrical Rough-In7/6/20157/6/20157/6/2015 10:05:18 AMAPASS
Check in with Security for visitors badge. Call Steve when in route. Phone #: ###-#### Inspection requested via web by Steve McCloy Lighting retro T-8 to UL listed LED 2x2 lay-in rough-in ok cover ceiling grid
ELE15-01547 Rough-In Permanent Service7/2/20157/6/20157/6/2015 9:22:49 AMAPASS
gary is the onsite contact at ###-#### Phone #: ###-#### Inspection requested via web by Tracy Robertson rough-in p/s u/g n ok
ELE15-01200 Final7/2/20157/6/20157/6/2015 9:21:02 AMAPASS
James is the onsite contact at ###-#### Phone #: ###-#### Inspection requested via web by Tracy Robertson final ok