Inspections for the day of: Monday, July 6, 2015.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD15-02214 FIRE-Final Inspection7/6/20157/6/20157/6/2015 3:25:13 PMPFAIL
Emergency egress lighting not installed in location on sales floor, location noted on city approved drawing, egress lighting to be installed and inspection called in when complete.
BLD15-02249 FIRE-Final Inspection7/6/20157/6/20157/6/2015 2:56:56 PMPFAIL
Fire extinguishers installed by tenant, have not been inspected by a licensed fire extinguisher contractor, once extinguishers are inspected tenant will request a new life fire safety inspection
BLD15-01398 FIRE-Final Inspection7/6/20157/6/20157/6/2015 11:12:12 AMPPASS
Life fire safety inspection passed/complete
FIR15-00419 INSP-Sprinkler Rough-in7/2/20157/6/20157/6/2015 9:18:27 AMAPASS
Rough in inspection passed/complete, tenant space approved for cover.
BLD15-02231 FIRE-Final Inspection7/2/20157/6/20157/6/2015 9:04:07 AMAFAIL
Fire sprinkler located in the back area of tenant space to far off of wall, head is 9ft 4in, does not meet acceptable spacing requirements for ordinary hazard, 130 square feet per head.