Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD17-02065 FIRE-Final Inspection7/5/20177/6/20177/6/2017 1:51:39 PMPFAIL
The fire alarm, fire sprinkler, hood suppression system and fire extinguishers are current with inspections. We found emergency lights that did not function and the green "nuclear" exit signs should have been replaced in 2016.

Sue Phone #: ###-#### or Racheal or Jennifer ###-####
FIR17-00146 INSP-Sprinkler Rough-in/Hydro7/5/20177/6/20177/6/2017 10:43:16 AMAPART
This was just a preliminary hydro test due to the fact that not all of the piping has been installed. A final hydro test of the overhead piping will be needed when the system installation is complete.
FIR17-00314 INSP-Final Inspection7/6/20177/6/20177/6/2017 9:07:12 AMAPASS
Permit finaled
FIR17-00088 INSP-Final Inspection7/5/20177/6/20177/6/2017 8:18:18 AMAPASS
Permit finaled
FIR17-00348 INSP-Sprinkler Rough-in7/5/20177/6/20177/6/2017 8:07:53 AMAPASS
Rough-in passed. Piping can be covered.
FIR17-00080 INSP-Sprinkler Rough-in7/5/20177/6/20177/6/2017 8:00:36 AMAPART
24 Hour Air test started at 8:00am with 46psi on the left system and 45 1/2psi on the right system.