BLD17-02065
| FIRE-Final Inspection | 7/5/2017 | 7/6/2017 | 7/6/2017 1:51:39 PM | P | FAIL |
|
|
The fire alarm, fire sprinkler, hood suppression system and fire extinguishers are current with inspections. We found emergency lights that did not function and the green "nuclear" exit signs should have been replaced in 2016.
Sue Phone #: ###-#### or Racheal or Jennifer ###-####
|
FIR17-00146
| INSP-Sprinkler Rough-in/Hydro | 7/5/2017 | 7/6/2017 | 7/6/2017 10:43:16 AM | A | PART |
|
|
This was just a preliminary hydro test due to the fact that not all of the piping has been installed. A final hydro test of the overhead piping will be needed when the system installation is complete.
|
FIR17-00314
| INSP-Final Inspection | 7/6/2017 | 7/6/2017 | 7/6/2017 9:07:12 AM | A | PASS |
|
|
Permit finaled
|
FIR17-00088
| INSP-Final Inspection | 7/5/2017 | 7/6/2017 | 7/6/2017 8:18:18 AM | A | PASS |
|
|
Permit finaled
|
FIR17-00348
| INSP-Sprinkler Rough-in | 7/5/2017 | 7/6/2017 | 7/6/2017 8:07:53 AM | A | PASS |
|
|
Rough-in passed. Piping can be covered.
|
FIR17-00080
| INSP-Sprinkler Rough-in | 7/5/2017 | 7/6/2017 | 7/6/2017 8:00:36 AM | A | PART |
|
|
24 Hour Air test started at 8:00am with 46psi on the left system and 45 1/2psi on the right system.
|