Inspections for the day of: Thursday, July 6, 2017.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR17-00264 INSP-Final Inspection7/5/20177/6/20177/6/2017 3:42:14 PMPPASS
Final fire alarm communicator inspection passed/complete
BLD16-01060 FIRE-Final Inspection7/6/20177/6/20177/6/2017 1:34:20 PMPFAIL
Documents for building fire safety and evacuation were not available at time of inspection as per note number 3 of the Building Permit Fire Code Review (BPFCR) comments. Signage for fire department access and fire lanes not installed as per note number 6 of BPFCR. Fire extinguishers are installed in cabinets but fire extinguishers do not have current inspection tags which are required as stated in note 10 of the BPFCR. Emergency egress lighting not installed in corridor on level 1, no exit discharge lighting installed on the exterior of the building at the exit discharge landings, lighting needs installed as stated in note 19 and 20 of the BPFCR. Numerous electrical box covers missing at time of inspection, covers need to be installed and secure before final life fire safey inspection. No signage on stairwell with roof access, signage needs to be installed stating stairwell with roof access. Fire alarm inspection could not be completed, no fire alarm drawings or small documents provided at time of inspection. Concrete has not been installed for discharge landings around building for egress purposes, exit discharge sidewalks need to be in place for final life fire safety inspection. Fire sprinkler permit needs to finaled before completion of life fire safety inspection (FIR permit for fire sprinkler inspection was called in by a seperate party, not the installing contractor, installing contractor is responsible for calling in their final inspection when ready). Rooms with an A occupancy need to have maximum occupancy signs installed, no occupancy signs installed at time of inspection. Ceiling tiles used for heat collection for fire sprinklers not installed at time of inspection, ceiling tiles need to be in place for final life fire safety inspection.
FIR17-00233 INSP-Final Inspection7/6/20177/6/20177/6/2017 1:04:35 PMPFAIL
City approved drawings and small documentation not on site.
FIR17-00308 INSP-Sprinkler Rough-in/Hydro7/6/20177/6/20177/6/2017 11:31:24 AMPFAIL
Fire sprinkler dead needs to be added or relocated to cover under stairs as shown on approved drawings. Fire sprinkler head in the southeast bedroom needs to be relocated to cover shadow area above closet area.
FIR16-00299 INSP-Sprinkler Rough-in7/3/20177/6/20177/6/2017 11:29:26 AMAPART
Rough to cover inspection for overhead fire sprinkler piping/pendant heads for the Laundry Chute, 10th floor conference room complete, approved for cover. Inspection request was also for fire pump commissioning, I stopped the fire pump commissioning, no water was flowed due to erosion issues (no curbing, loose dirt that would have been washed out, nearest storm drain was downstream from a dirt pile)
BLD17-01489 FIRE-Final Inspection7/5/20177/6/20177/6/2017 8:33:43 AMAPASS
No fire sprinkler modifications, no fire alarm modifications, fire extinguishers are in place with current inspection tags. Final life fire safety inspection for area of work complete.
FIR17-00308 INSP-Sprinkler Rough-in/Hydro6/30/20177/6/20177/6/2017 7:50:55 AMACANC
Please call Jake when heading out, thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello