ELE18-00727
| Final | 7/6/2018 | 7/6/2018 | 7/6/2018 3:19:36 PM | P | PART |
|
|
Temp final for training inspection. Please make it later in the afternoon after 3 if possible or if necessary. Phone #: ###-#### Inspection requested via web by Tom Jenkins All GFCI protection in place an tested OK. Signed TCO line on card.
|
ELE17-02862
| Electrical Rough-In | 7/6/2018 | 7/6/2018 | 7/6/2018 12:12:06 PM | A | PASS |
|
|
units 309 , 310 , 311 , 312 , 316 , hallway , and storage Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty Rooms and areas noted rough in ok cover
|
ELE18-00727
| Conference | 7/5/2018 | 7/6/2018 | 7/6/2018 12:11:14 PM | A | DONE |
|
|
Phone #: ###-#### Inspection requested via web by Tom Jenkins Discussed and double checked all requirement for temp occupancy. All 1,2,3 pole receptacles shall have GFCI protection or be hard wired with disconnecting means installed. If this cannot be accomplished all power to the receptacles for the appliances needing GFCI protection shall be diconnected or be locked out so appliance cannot be used until code compliant.
|
ELE18-02477
| Conference | 7/2/2018 | 7/6/2018 | 7/6/2018 10:08:44 AM | A | DONE |
|
|
John Phone #: ###-#### Informed owner he is required to do work. Planning a single circuit to shed in back yard, 12" min. if GFCI protected, additional depth if not protected or additional circuits are added. Discussed tamper and weather resistant types for locations, and disconnecting means for seperate structure. Sch 80 needed where emerge from grade
|
ELE17-02649
| Electrical Rough-In | 7/5/2018 | 7/6/2018 | 7/6/2018 9:34:27 AM | A | PASS |
|
|
Contact is Brian Wilhite. Phone #: ###-#### Inspection requested via web by Scott Campbell Break room 138, Men's toilet 137, Women's toilet 136, Office 135 only grid rough in ok cover
|
ELE18-01699
| Final | 7/5/2018 | 7/6/2018 | 7/6/2018 9:03:51 AM | A | FAIL |
|
|
garage code 2468 Phone #: ###-#### Inspection requested via web by Darryn Coburn 210.8- GFCI decive shall be located where readily accessible. Unable to locate GFCI to test tub unable to remove cover due to type of screw used. If located behind cover shall be relocated to an area where it does not take tools to access it.
|
ELE18-01598
| Final | 7/5/2018 | 7/6/2018 | 7/6/2018 8:40:01 AM | A | PASS |
|
|
garage code 2468 Phone #: ###-#### Inspection requested via web by Darryn Coburn Final ok
|