Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-00727 Final7/6/20187/6/20187/6/2018 3:19:36 PMPPART
Temp final for training inspection. Please make it later in the afternoon after 3 if possible or if necessary. Phone #: ###-#### Inspection requested via web by Tom Jenkins
All GFCI protection in place an tested OK. Signed TCO line on card.
ELE17-02862 Electrical Rough-In7/6/20187/6/20187/6/2018 12:12:06 PMAPASS
units 309 , 310 , 311 , 312 , 316 , hallway , and storage Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty Rooms and areas noted rough in ok cover
ELE18-00727 Conference7/5/20187/6/20187/6/2018 12:11:14 PMADONE
Phone #: ###-#### Inspection requested via web by Tom Jenkins
Discussed and double checked all requirement for temp occupancy. All 1,2,3 pole receptacles shall have GFCI protection or be hard wired with disconnecting means installed. If this cannot be accomplished all power to the receptacles for the appliances needing GFCI protection shall be diconnected or be locked out so appliance cannot be used until code compliant.
ELE18-02477 Conference7/2/20187/6/20187/6/2018 10:08:44 AMADONE
John Phone #: ###-####
Informed owner he is required to do work. Planning a single circuit to shed in back yard, 12" min. if GFCI protected, additional depth if not protected or additional circuits are added. Discussed tamper and weather resistant types for locations, and disconnecting means for seperate structure. Sch 80 needed where emerge from grade
ELE17-02649 Electrical Rough-In7/5/20187/6/20187/6/2018 9:34:27 AMAPASS
Contact is Brian Wilhite. Phone #: ###-#### Inspection requested via web by Scott Campbell
Break room 138, Men's toilet 137, Women's toilet 136, Office 135 only grid rough in ok cover
ELE18-01699 Final7/5/20187/6/20187/6/2018 9:03:51 AMAFAIL
garage code 2468 Phone #: ###-#### Inspection requested via web by Darryn Coburn
210.8- GFCI decive shall be located where readily accessible. Unable to locate GFCI to test tub unable to remove cover due to type of screw used. If located behind cover shall be relocated to an area where it does not take tools to access it.
ELE18-01598 Final7/5/20187/6/20187/6/2018 8:40:01 AMAPASS
garage code 2468 Phone #: ###-#### Inspection requested via web by Darryn Coburn Final ok