ELE98-03123
| INSP - Electrical Rough-In | 7/6/1999 | 7/7/1999 | 7/7/1999 12:00:00 AM | A | PART |
|
|
07/06/99 403 - 1ST AND 5TH FLOOR ###-#### ..trans jms.. WALLS ELE R/I.
|
ELE99-01740
| INSP - Final | 7/6/1999 | 7/7/1999 | 7/7/1999 12:00:00 AM | A | FAIL |
|
|
07/06/99 403 - please call ###-#### first to meet there NEC: 210-52(B)(2). SMALL APPLAINCE BRANCH CIRCUITS SHALL HAVE NO OTHER
|
ELE99-02331
| INSP - Electrical Rough-In | 7/7/1999 | 7/7/1999 | 7/7/1999 12:00:00 AM | P | FAIL |
|
|
07/07/99 403 - WAYNE - ###-#### R/I WALL COVERING NEC: 517-3. REDUNDANT GROUNDING REQUIRED IN PATIENT CARE AREAS LOWER THAN 7 AND 1/2 FT.
|
ELE99-02361
| INSP - Electrical Rough-In | 7/7/1999 | 7/7/1999 | 7/7/1999 12:00:00 AM | P | PASS |
|
|
07/07/99 403 - BOB - ###-#### PERM/SVC; ELE R/I.
|
ELE99-00649
| INSP - Final | 7/7/1999 | 7/7/1999 | 7/7/1999 12:00:00 AM | P | PASS |
|
|
07/07/99 403 - Cameron ###-#### OK
|