InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00139 FIR-Aging Inspection7/7/20037/7/20037/7/2003 12:00:00 AM PASS
work is still in progress 7/7/2003 8:03:59 AM
BLD02-00090 FIRE-Final Inspection7/7/20037/7/20037/7/2003 12:00:00 AMPCANC
john; Phone #: ###-#### Internet Inspection Request from: Barbara Moore received call from Allen and he said they won't be ready until 7/8 and he would reschedule 7/7/2003 3:45:13 PM
FIR03-00123 INSP-Sprinkler Rough-in/Hydro7/7/20037/7/20037/7/2003 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 7/7/2003 at 10:45:26 AM. Contact: ###-####. wet and antifreeze systems will require annual inspection; heads overspaced above ceiling in kitchen per plan review notes; mezzanine area not fully sprinklered; head obstructed by partition in mens room; remove paper from heads throughout; sprinklers or noncumbustible area by dishwasher along wall; repair head in storage room; submit data for fire pump to plan review 7/7/2003 3:38:26 PM