Inspections for the day of: Wednesday, July 7, 2004.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00189 FIR-Aging Inspection7/7/20047/7/20047/7/2004 12:00:00 AM PASS
Talked to Peter and this will be ready for inspection within the next few days 7/7/2004 9:56:55 AM
BLD03-01845 BLD-Aging Inspection7/7/20047/7/20047/7/2004 12:00:00 AM PASS
Larry Durkin is out this week; scheduled a follow up conference for 7/12/04 7/7/2004 12:51:13 PM
FIR04-00259 INSP-Alarm Testing7/5/20047/7/20047/7/2004 12:00:00 AMAPASS
Cell Ph. ###-####; Phone #: ###-#### Internet Inspection Request from: Daniel Buccino
BLD04-00885 FIRE-Final Inspection7/6/20047/7/20047/7/2004 12:00:00 AMAFAIL
harry; Phone #: ###-#### Internet Inspection Request from: Annette Moore Sprinkler work in new conference room without sprinkler permit; exiting from the bullpen area is over 100 ft to corridor exit so a second exit is needed through new training room through the 2 hr horizontal exit; exit sign to be added out of bullpen with proper hardware; this was through meeting with Paul M. 7/7/2004 2:57:55 PM
FIR03-00814 INSP-Sprinkler Rough-in/Hydro7/6/20047/7/20047/7/2004 12:00:00 AMPPASS
Phone #: ###-#### Internet Inspection Request from: Trent Bice UG permit completed for flush/hydro and cover; scope of this permit shows 6 inch for UG as 8 inch is installed; will need UG submittals at job site to close this permit out 7/7/2004 1:06:13 PM
FIR03-00211 INSP-Final Inspection7/6/20047/7/20047/7/2004 12:00:00 AMPPASS
steve; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
BLD03-00960 FIRE-Final Inspection7/7/20047/7/20047/7/2004 12:00:00 AMPPASS
BLD04-00422 FIRE-Final Inspection7/7/20047/7/20047/7/2004 12:00:00 AMPFAIL
Occupant load sign; rated access door for dampers in shaft on third floor; extinguisher; skirting around top of refer unit; sprinkler obstruction in north corner by storage too close to head 7/7/2004 4:24:00 PM
FIR04-00369 INSP-Sprinkler Rough-in/Hydro7/7/20047/7/20047/7/2004 12:00:00 AMPPASS
Phone #: ###-#### Internet Inspection Request from: Cliff Miller Addrees is 223 6th St. 7/7/2004 4:19:20 PM