BLD03-01020
| BLD-Aging Inspection | 7/7/2005 | 7/7/2005 | 7/8/2005 3:29:48 PM | | DONE |
|
|
Left message with Dennis at ###-#### for requirements to final this permit.
|
FIR05-00228
| INSP-Final Inspection | 7/6/2005 | 7/7/2005 | 7/7/2005 2:44:21 PM | A | FAIL |
|
|
HVAC units are inoperable, unable to verify functionality of duct smoke detection devices until units can be run.
|
FIR05-00099
| INSP-Final Inspection | 7/6/2005 | 7/7/2005 | 7/7/2005 1:31:20 PM | A | FAIL |
|
|
Provide sign at FACP door and fire riser door, provide hd cut sheet, provide lock and label at FACP breaker, verify mag lock function on main doors when installed, provide list of signal verification from central station, provide device location map at panel.
|
FIR05-00045
| INSP-Final Inspection | 7/6/2005 | 7/7/2005 | 7/7/2005 1:26:03 PM | A | FAIL |
|
|
Repair outside bell, perform forward flow test, provide heads, head wrench, and NFPA 25 in head box, provide sinage on all valves in riser room, install ceiling tile and canopies prior to final.
|
BLD05-00876
| FIRE-Final Inspection | 7/6/2005 | 7/7/2005 | 7/7/2005 8:32:11 AM | A | PASS |
|
|
Fire life safety finaled.
|