Inspections for the day of: Friday, July 7, 2006.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00493 INSP-Final Inspection7/7/20067/7/20067/10/2006 12:25:25 PMPPASS
The hood suppression system functioned properly under test conditions.
BLD05-03413 FIRE-Final Inspection7/7/20067/7/20067/7/2006 3:07:39 PMPPASS
Fire life safety correction notice items have been completed, inspection passed.
FIR06-00198 INSP-Final Inspection7/6/20067/7/20067/7/2006 2:52:13 PMPFAIL
Noted several issues including overspaced head, blocked coverage by ductwork in several locations, incorrect temp ratings at the kitchen hood area, missing ssp in the mech. closet, one head with bent deflector needs to be replaced, min. spacing between heads is exceeded at one location. Inspection concluded at the first floor due to number of defficiencies, no inspection done for the basement area at this time.
FIR06-00465 INSP-Final Inspection7/6/20067/7/20067/7/2006 12:44:15 PMANR
Project not ready for inspection at this time.
BLD06-01536 FIRE-Final Inspection7/6/20067/7/20067/7/2006 12:42:36 PMAPASS
Life safety inspection passed.
FIR06-00464 INSP-Final Inspection7/6/20067/7/20067/7/2006 12:42:08 PMAPASS
Fire sprinkler permit finaled.
BLD06-00469 FIRE-Final Inspection7/6/20067/7/20067/7/2006 11:53:51 AMAPASS
Fire life safety is acceptable.
FIR06-00456 INSP-Final Inspection7/6/20067/7/20067/7/2006 11:52:45 AMAPASS
OH fire sprinkler work is satisfactory, inspection passed, permit finaled.
FIR05-00659 INSP-Sprinkler Rough-in7/6/20067/7/20067/7/2006 11:51:23 AMAPART
Tie-ins to existing system at the west office area are acceptable to cover.
BLD05-03413 FIRE-Final Inspection7/6/20067/7/20067/7/2006 12:00:00 AMACANC
Joe; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
FIR06-00198 INSP-Final Inspection7/6/20067/7/20067/6/2006 2:53:27 PMACANC
Final Inspection; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley