FIR06-00493
| INSP-Final Inspection | 7/7/2006 | 7/7/2006 | 7/10/2006 12:25:25 PM | P | PASS |
|
|
The hood suppression system functioned properly under test conditions.
|
BLD05-03413
| FIRE-Final Inspection | 7/7/2006 | 7/7/2006 | 7/7/2006 3:07:39 PM | P | PASS |
|
|
Fire life safety correction notice items have been completed, inspection passed.
|
FIR06-00198
| INSP-Final Inspection | 7/6/2006 | 7/7/2006 | 7/7/2006 2:52:13 PM | P | FAIL |
|
|
Noted several issues including overspaced head, blocked coverage by ductwork in several locations, incorrect temp ratings at the kitchen hood area, missing ssp in the mech. closet, one head with bent deflector needs to be replaced, min. spacing between heads is exceeded at one location. Inspection concluded at the first floor due to number of defficiencies, no inspection done for the basement area at this time.
|
FIR06-00465
| INSP-Final Inspection | 7/6/2006 | 7/7/2006 | 7/7/2006 12:44:15 PM | A | NR |
|
|
Project not ready for inspection at this time.
|
BLD06-01536
| FIRE-Final Inspection | 7/6/2006 | 7/7/2006 | 7/7/2006 12:42:36 PM | A | PASS |
|
|
Life safety inspection passed.
|
FIR06-00464
| INSP-Final Inspection | 7/6/2006 | 7/7/2006 | 7/7/2006 12:42:08 PM | A | PASS |
|
|
Fire sprinkler permit finaled.
|
BLD06-00469
| FIRE-Final Inspection | 7/6/2006 | 7/7/2006 | 7/7/2006 11:53:51 AM | A | PASS |
|
|
Fire life safety is acceptable.
|
FIR06-00456
| INSP-Final Inspection | 7/6/2006 | 7/7/2006 | 7/7/2006 11:52:45 AM | A | PASS |
|
|
OH fire sprinkler work is satisfactory, inspection passed, permit finaled.
|
FIR05-00659
| INSP-Sprinkler Rough-in | 7/6/2006 | 7/7/2006 | 7/7/2006 11:51:23 AM | A | PART |
|
|
Tie-ins to existing system at the west office area are acceptable to cover.
|
BLD05-03413
| FIRE-Final Inspection | 7/6/2006 | 7/7/2006 | 7/7/2006 12:00:00 AM | A | CANC |
|
|
Joe; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
|
FIR06-00198
| INSP-Final Inspection | 7/6/2006 | 7/7/2006 | 7/6/2006 2:53:27 PM | A | CANC |
|
|
Final Inspection; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
|