Inspections for the day of: Friday, July 7, 2006.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD06-00400 FIRE-Final Inspection7/6/20067/7/20067/7/2006 4:08:49 PMPFAIL
The shell/core has not been called in for a final yet.
BLD04-00917 FIRE-Final Inspection7/6/20067/7/20067/7/2006 4:06:10 PMPFAIL
No approved plans on site.
BLD06-01009 FIRE-Final Inspection7/7/20067/7/20067/7/2006 2:34:57 PMPFAIL
I spoke to contractor about the approved hardware that is required for the two doors that exit the cashiers office. He stated that he would get it changed this weekend and would call in a new inspection for next week.
FIR05-00827 INSP-Final Inspection7/7/20067/7/20067/7/2006 2:32:54 PMAPART
The second floor sprinkler system is completed and approved.
FIR05-00800 INSP-Final Inspection7/6/20067/7/20067/7/2006 2:31:53 PMAFAIL
This inspection was for occupancy on the second floor. Before approval for the second floor the manual pull station at the east stairwell needs to be lowered and the smoke detector near the elevator lobby reception desk needs relocated away from the supply grill. I also need a print out of the signals that ADT received and to test the supervision of the new NAC panel on the second floor. First floor will need to be tested and the smoke fire damper on the fifth floor. Elevator recall functioned correctly for the machine room, shaft, first floor and second floor.
BLD05-01937 FIRE-Final Inspection7/6/20067/7/20067/7/2006 12:23:23 PMAPASS
Life safety finaled
FIR05-00830 INSP-Final Inspection7/5/20067/7/20067/7/2006 12:22:53 PMAPASS
Permit finaled
FIR06-00086 INSP-Final Inspection7/6/20067/7/20067/7/2006 12:22:36 PMAPASS
permit finaled
BLD05-03256 FIRE-Final Inspection7/6/20067/7/20067/7/2006 10:54:29 AMAFAIL
Fire alarm permit failed so life safety can not be finaled yet.
FIR06-00082 INSP-Final Inspection7/7/20067/7/20067/7/2006 10:53:48 AMPFAIL
Provide smoke detection for the Liebert unit and test the remaining two induct smoke detectors.