BLD03-01020
| BLD-Aging Inspection | 7/7/2008 | 7/7/2008 | 7/9/2008 10:51:23 AM | | DONE |
|
|
Pending fire sprinkler permit final- verification of system main control valve supervision.
|
FIR08-00383
| INSP-Final Inspection | 7/2/2008 | 7/7/2008 | 7/8/2008 12:14:14 PM | P | DEFR |
|
|
Scheduled by a contractor via Hello! on 7/2/2008 at 5:17:01 PM. Contact: ###-####. Inspection rescheduled per request by contractor.
|
FIR08-00384
| INSP-Final Inspection | 7/2/2008 | 7/7/2008 | 7/8/2008 12:11:32 PM | P | DEFR |
|
|
Scheduled by a contractor via Hello! on 7/2/2008 at 5:16:15 PM. Contact: ###-####. Inspection rescheduled per contractor request.
|
BLD08-00681
| FIRE-Final Inspection | 7/7/2008 | 7/7/2008 | 7/7/2008 3:41:21 PM | P | PASS |
|
|
Life safety inspection passed, doors and hardware at three locations to be replaced per contractor and verified prior to structural final.
|
FIR08-00369
| INSP-Supply line flush | 7/3/2008 | 7/7/2008 | 7/7/2008 2:27:34 PM | P | NR |
|
|
tony/brian ###-#### Note: 1:00 Phone #: ###-#### Inspection rescheduled per conversation with contractor.
|
FIR06-00595
| INSP-Final Inspection | 7/3/2008 | 7/7/2008 | 7/7/2008 2:26:43 PM | A | FAIL |
|
|
Reviewed and reinspected defficient items noted at the previous inspection including elevator shunt trip power supervision, recall for car #3, new FJ at the pump room, new antifreeze system tamper, flow switch at the NE 2nd floor stairway, tampers at riser and floor control valves. Two remaining items in need of repair include the 5th floor NE tamper at the OS&Y sprinkler control valve, and provision for a flashing fire hat at the elevator cars upon FA device activation in the hoistway or machine room.
|
FIR08-00320
| INSP-Final Inspection | 7/3/2008 | 7/7/2008 | 7/7/2008 11:40:57 AM | A | PASS |
|
|
Scope of work completed satisfactory, fire sprinkler permit finaled.
|
BLD07-00813
| FIRE-Final Inspection | 7/2/2008 | 7/7/2008 | 7/7/2008 11:14:47 AM | A | PASS |
|
|
Fire life safety final inspection passed.
|
FIR07-00437
| INSP-Final Inspection | 7/2/2008 | 7/7/2008 | 7/7/2008 11:14:10 AM | A | PASS |
|
|
Correction notice items verified for completion, fire sprinkler permit work finaled.
|
FIR08-00369
| INSP-Supply line flush | 7/1/2008 | 7/7/2008 | 7/2/2008 7:16:29 AM | A | CANC |
|
|
Scheduled by a contractor via Hello! on 7/1/2008 at 11:35:54 AM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Jul 2 2008 7:16AM.
|