Inspections for the day of: Tuesday, July 7, 2009.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDoug A Poedy
TitleELE-INSPECTOR
Phone #447-7209
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE08-02970 ELE-Aging Inspection7/7/20097/7/20097/15/2009 9:42:21 AM DONE
Not quite ready but close. Darren said they should have it done this week.
ELE09-00799 Electrical Rough-In7/7/20097/7/20097/7/2009 5:01:10 PMPPART
Jason Phone #: ###-#### Area A ok to cover ceiling.
ELE09-01193 Final7/7/20097/7/20097/7/2009 3:39:46 PMPFAIL
Shed sits behind house. You may go behind
house and do not need to contact the residence since it is a rental.
Phone #: ###-#### Internet Inspection Request from: Dave Friend. Correction notice posted. NEC 110.12 Unused openings shall be closed,NEC 344.46 Where a conduit enters a box a bushing shall be provided for abrasion protection.NEC 334.15(B) Exposed NM cable shall be protected from physical damage,NEC 210.4(B) Multiwire branch circuits shall disconnect simultaneously,NEC 300.5 direct buried conduit shall be installed to meet the minimum cover requirements of table 300.5.
ELE09-01182 Electrical Rough-In7/6/20097/7/20097/7/2009 2:36:10 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Shawn Kelley. Ok to cover.
ELE09-01170 Electrical Rough-In7/6/20097/7/20097/7/2009 1:43:08 PMPPASS
Scheduled by a contractor via Hello! on 7/6/2009 at 2:19:41 PM. Contact: ###-####. Ok to cover walls. No esc permit.
ELE09-01144 Electrical Rough-In7/7/20097/7/20097/7/2009 1:08:26 PMPPASS
Dave Phone #: ###-#### Ok to cover. Did a survey on a tear in outer insulation and a box needing secured better. Notifiied dave.No esc permit.
ELE09-01183 Permanent Service7/6/20097/7/20097/7/2009 11:49:51 AMADONE
Existing service inspection so power can be restored to building - Call Lloyd 1/2 hour before inspection, I''ll meet you there. Phone #: ###-#### Internet InspectionRequest from: Lloyd Looney Told Lloyd that the 400 amp panel needed a UL appr. dead man cover or that he needed to replace it.
ELE09-01171 Temporary Service7/6/20097/7/20097/7/2009 10:45:23 AMAPASS
Call Brad if any questions. Phone #: ###-#### Internet Inspection Request from: Bill Hines.
ELE09-00914 Final7/6/20097/7/20097/7/2009 9:42:58 AMAPASS
Please call 10 or 15 minutes ahead so we can meet at job site. Phone #: ###-#### Internet Inspection Request from: mark morris. Ok final. No esc permit.
ELE07-03020 Conference7/6/20097/7/20097/7/2009 9:02:22 AMADONE
Jay Parks ###-####//call 30 min prior to meet. Jay wants to put service underground. We talked about different ways to accomplish this.
ELE09-01188 Temporary Service7/7/20097/7/20097/7/2009 12:00:00 AMPCANC
contact: Bob Schroder Phone #: ###-#### Internet Inspection Request from: Julie Schroder